Profibus pa, 4 technical data, Hardware – KROHNE OPTIWAVE 5200 PROFIBUS User Manual
Page 5: Software
PROFIBUS PA
2
5
OPTIWAVE 5200 C
www.krohne.com
10/2013 - 4003066901 - MA OPTIWAVE5200C-PA-R01-en-
The device has 4 slots. The Analog Input Function Blocks use slot 1 (as a virtual module). The
user cannot change this setting. But the user can change the measurement name and unit for
each Function Block. Refer to the table that follows:
The calibration units are used as default units.
2.4 Technical data
INFORMATION!
If it is necessary to change the measurement name, change the channel parameter in the acyclic
PROFIBUS services.
Slot Module
type
Measurement name
Unit
1
AI-FB
Level (default setting)
mm
1
Distance
mm
1
Conversion
L
1
Conversion Distance
L
1
1 Default measurement unit
Hardware
Type
PROFIBUS MBP interface. This interface agrees with IEC 61158-2 (bit rate
31.25 kbit/s);
voltage mode (MBP = Manchester-Coded, Bus-Powered)
Device power supply
9...32 V - bus powered; no additional power supply required
Polarity sensitivity
No
Base current
14 mA
FDE
Yes. The Fault Disconnection Electronics (FDE) operates independently.
Max. error current
20.5 mA
Start current after 10 ms Lower than base current
Software
Supported GSD
KR014554.GSD
PA139700.GSD
Device profile
PROFIBUS PA Profile V3.02; conformance class B, compact
Address setting
Default:
126
Hardware DIP switch:
0…125
PROFIBUS service Set_Slave_Add:
0...125
Factory_Reset=2712:
126
Write protection
Password and/or hardware switch
SAPs
2 × MS1 SAPs – acyclic interface to PLC
3 × MS2 SAPs – the number of MS2 Service Access Points is usually equal to
the maximum number of master class 2 tools
Function blocks
1 Physical Block
1 Level Transducer Block
4 Analog Input Function Blocks