Profibus pa, 4 technical data, Hardware – KROHNE OPTIWAVE 5200 PROFIBUS User Manual

Page 5: Software

background image

PROFIBUS PA

2

5

OPTIWAVE 5200 C

www.krohne.com

10/2013 - 4003066901 - MA OPTIWAVE5200C-PA-R01-en-

The device has 4 slots. The Analog Input Function Blocks use slot 1 (as a virtual module). The
user cannot change this setting. But the user can change the measurement name and unit for
each Function Block. Refer to the table that follows:

The calibration units are used as default units.

2.4 Technical data

INFORMATION!
If it is necessary to change the measurement name, change the channel parameter in the acyclic
PROFIBUS services.

Slot Module

type

Measurement name

Unit

1

AI-FB

Level (default setting)

mm

1

Distance

mm

1

Conversion

L

1

Conversion Distance

L

1

1 Default measurement unit

Hardware

Type

PROFIBUS MBP interface. This interface agrees with IEC 61158-2 (bit rate
31.25 kbit/s);
voltage mode (MBP = Manchester-Coded, Bus-Powered)

Device power supply

9...32 V - bus powered; no additional power supply required

Polarity sensitivity

No

Base current

14 mA

FDE

Yes. The Fault Disconnection Electronics (FDE) operates independently.

Max. error current

20.5 mA

Start current after 10 ms Lower than base current

Software

Supported GSD

KR014554.GSD
PA139700.GSD

Device profile

PROFIBUS PA Profile V3.02; conformance class B, compact

Address setting

Default:

126

Hardware DIP switch:

0…125

PROFIBUS service Set_Slave_Add:

0...125

Factory_Reset=2712:

126

Write protection

Password and/or hardware switch

SAPs

2 × MS1 SAPs – acyclic interface to PLC
3 × MS2 SAPs – the number of MS2 Service Access Points is usually equal to
the maximum number of master class 2 tools

Function blocks

1 Physical Block
1 Level Transducer Block
4 Analog Input Function Blocks