3 Electrical connection

To open the terminal compartment of the signal converter, first open the safety lock
with an Allen key (size: 4 mm) and then use the enclosed special wrench to turn the
cover anticlockwise.

Supply power

Variant

Voltage range

Recommended fuse protection

24 V DCAC

19.2 - 28.8 V DC or
20.4 - 26.4 V AC

min. T 0.5 A


Terminal assignment

Supply power:


Terminal compartment BM 700: External power supply "FEAS, type PSLC242":



Power supply galvanically insulated according to VDE 0551
Dimensions (W×H×D): 55Ч75Ч110 mm, usable for rail
mounting

Class of protection
The BM 700 level gauge is designed for safety class 1 in conformity with VDE 0106
Part 1.

24 V DCAC supply
When connected to a “functional extra-low voltage with safety separation“ power
source (SELV or PELV) in accordance with VDE 0100, Part 410 or equivalent
(inter)national regulations, connection of a safety conductor (PE) is not required.

Equipotential bonding
When used in hazardous areas, the BM 700 Ex must be incorporated in the PA
equipotential bonding system
, irrespective of the type of power supply! If the PA is
connected via a separate conductor, this must be connected to the separate U-clamp
terminal at the “neck“ of the BM 700 Ex. Cancellation of equipotential bonding is only
permitted when the BM 700 is disconnected from supply.

Rated temperature of connecting cables: see Section 6.

+ +

- -

L1L1

N N

3 4

230 V AC

BM 700 (max. 5 instruments)

+ +

- -

L1L1

N N

3 4

115 V AC

BM 700 (max. 5 instruments)

32 31

-

+

Current
output

1

2

- +

4-20mA

max.350

Power supply

24 V DC (+/-20%)

24 V AC (+10/-15%)

or

< 300 mA