Limits of

temperature at flange:

Version

Minimum flange temperature

Maximum flange temperature


(1)+(2) of the
type code


Standard
version


Special version
with marking
„2.4610“ at the
Metaglas ring


Without high
temperature
distance piece


With high
temperature
distance piece

V96 ... FFKM

- 30°C (- 22°F)

- 60°C (-76°F) +130°C (+266°F) +250°C (+482°F)

V96 ... K2035

- 30°C (- 22°F)

- 60°C (-76°F) +130°C (+266°F) +210°C (+410°F)

V96 ... FPM

- 30°C (- 22°F)

- 60°C (-76°F) +130°C (+266°F) +200°C (+392°F)

V96 ... FEP

- 30°C (- 22°F)

- 60°C (-76°F) +130°C (+266°F) +200°C (+392°F)

WS LPTFE

- 40°C (- 40°F)

–––

+130°C (+266°F) +150°C (+302°F)

WS PTFE

- 40°C (- 40°F)

–––

+130°C (+266°F) +150°C (+302°F)

WS SS PTFE

- 20°C (- 4°F)

–––

+130°C (+266°F) +150°C (+302°F)

WS SS PP

- 20°C (- 4°F)

–––

+100°C (+212°F) +100°C (+212°F)

9 Parameter check list BM 700

Menu item changed on Version:

Fct. Configuration parameters (extract)

3.1.1 Tank height

3.1.2 Block distance

3.1.3 Antenna

3.1.4 Antenna extension

3.1.5 Distance piece

3.1.6 Stillwell / diameter

3.1.7 Reference offset

3.1.8 Tank bottom

3.3.1 Current output, function offset

3.3.2 Current output range/error

3.3.3 Min. current scale

3.3.4 Max. current scale

3.5.2 Empty spectrum

3.5.3 Time constant

3.5.4 Tracking speed

3.5.5 Multiple reflections (yes/no)

3.5.6 Block distance ident (yes/no)

3.5.7 Function FTB

3.5.8 Epsilon R

3.5.9 Tank type