BM 700 Installation and Operating Instructions Page 11
Function (Fct.)
Input range
Description
3.3 SIGNAL OUT
3.3.1 FUNCTION I
Select OFF/LEVEL/DISTANCE
/CONVERSION//SW.OUTP.
Select function of the current output.
3.3.2 RANGE I
Select 4-20mA
4-20mA/E2
4-20mA/E22
Select range/error status for the current
output (hold last value or 2mA / 22mA
in error status).
3.3.3 SCALE 4mA
Enter -200.00 ... +200.00 [m]
0.00 ... 99999.99 [m
3
]
Enter lower measuring range value for
the current output (4 mA).
(see explanatory notes)
3.3.4 SCALE 20mA
Enter -200.00 ... +200.00 [m]
0.00 ... 99999.99 [m
3
]
Enter full-scale range value for the
current output (20 mA).
(see explanatory notes)
3.3.5 BAUDRATE
Select 1200 Bd
Baud rate for HART communication
(non-changeable).
3.3.6 ADDRESS
Enter 0 ... 255 Enter device address.
(for HART multidrop)
3.3.7 PROTOCOL
Select
HART/KROHNE-PC
Select communications protocol
3.4 USER DATA
3.4.1 LANGUAGE
Select GB-USA/D/F/I/E/P/S Select language for the optional
display.
3.4.2 ENTRY CODE 1
Select NO/YES Switch the access lockout on/off.
If YES, for every access a 9-digit entry
code on the 3 keys is necessary.
3.4.3 CODE 1
Enter code (RRREEEUUU) Enter the entry code for access lockout.
3.4.4 LOCATION
Enter text (8 characters)
Enter a device identifier.
3.5 APPLICAT.
3.5.1 AUTO TANKH.
Special function
Automatic determination of tank height
(see explanatory notes).
3.5.2 EMPTY.SPEC.
Select OFF/ON/
RECORD
Recording the profile of the empty tank
(empty-tank spectrum) (see explana-
tory notes).
3.5.3 TIMECONST.
Value 1...10...100 [s] Enter time constant for measured-value
filtering
3.5.4 TRACING.VEL.
Value
0.01...0.50...10.00 [m/Min]
Enter the maximum rate of change in
level that can occur in operation.
3.5.5 MULT.REFL.
Select NO/YES Switch the multi-reflection identifier
on/off.
3.5.6 BD-DETECT.
Select NO/YES Switch the block distance (overfill)
identifier on/off (see explanatory notes).
3.5.7 FUNCT. FTB
Select OFF/
PARTIAL
Select function of tank bottom tracing
system (see explanatory notes).
3.5.8 EPSILON R
Enter
1.1000 ... 8.0000
Enter relative permittivity of product
(only for Fct. 3.5.7)
3.5.9 TANKTYPE
Select STORAGE T./
PROC TANK
Select tank type.
STORAGE T. = smooth product surface
PROC TANK = slightly disturbed pro-
duct surface
Default values are shown in bold type in the table.