BM 700 Installation and Operating Instructions Page 11

Function (Fct.)

Input range

Description

3.3 SIGNAL OUT

3.3.1 FUNCTION I

Select OFF/LEVEL/DISTANCE
/CONVERSION//SW.OUTP.

Select function of the current output.

3.3.2 RANGE I

Select 4-20mA
4-20mA/E2
4-20mA/E22

Select range/error status for the current
output (hold last value or 2mA / 22mA
in error status).

3.3.3 SCALE 4mA

Enter -200.00 ... +200.00 [m]
0.00 ... 99999.99 [m

3

]

Enter lower measuring range value for
the current output (4 mA).
(see explanatory notes)

3.3.4 SCALE 20mA

Enter -200.00 ... +200.00 [m]
0.00 ... 99999.99 [m

3

]

Enter full-scale range value for the
current output (20 mA).
(see explanatory notes)

3.3.5 BAUDRATE

Select 1200 Bd

Baud rate for HART communication
(non-changeable).

3.3.6 ADDRESS

Enter 0 ... 255 Enter device address.

(for HART multidrop)

3.3.7 PROTOCOL

Select
HART/KROHNE-PC

Select communications protocol

3.4 USER DATA

3.4.1 LANGUAGE

Select GB-USA/D/F/I/E/P/S Select language for the optional

display.

3.4.2 ENTRY CODE 1

Select NO/YES Switch the access lockout on/off.

If YES, for every access a 9-digit entry
code on the 3 keys is necessary.

3.4.3 CODE 1

Enter code (RRREEEUUU) Enter the entry code for access lockout.

3.4.4 LOCATION

Enter text (8 characters)

Enter a device identifier.

3.5 APPLICAT.

3.5.1 AUTO TANKH.

Special function

Automatic determination of tank height
(see explanatory notes).

3.5.2 EMPTY.SPEC.

Select OFF/ON/
RECORD

Recording the profile of the empty tank
(empty-tank spectrum) (see explana-
tory notes).

3.5.3 TIMECONST.

Value 1...10...100 [s] Enter time constant for measured-value

filtering

3.5.4 TRACING.VEL.

Value
0.01...0.50...10.00 [m/Min]

Enter the maximum rate of change in
level that can occur in operation.

3.5.5 MULT.REFL.

Select NO/YES Switch the multi-reflection identifier

on/off.

3.5.6 BD-DETECT.

Select NO/YES Switch the block distance (overfill)

identifier on/off (see explanatory notes).

3.5.7 FUNCT. FTB

Select OFF/
PARTIAL

Select function of tank bottom tracing
system (see explanatory notes).

3.5.8 EPSILON R

Enter
1.1000 ... 8.0000

Enter relative permittivity of product
(only for Fct. 3.5.7)

3.5.9 TANKTYPE

Select STORAGE T./
PROC TANK

Select tank type.
STORAGE T. = smooth product surface
PROC TANK = slightly disturbed pro-
duct surface

Default values are shown in bold type in the table.