KROHNE BM 700 EN User Manual
Page 10
Page 10 BM 700 Installation and Operating Instructions
Configuration menu (version 5.00 / 5.01)
Function (Fct.)
Input range
Description
1.0 OPERATION
1.1 DISPLAY
1.1.1 FCT.DISP
identical with 3.2.1
1.1.2 UNIT.LENGTH
identical with 3.2.2
1.1.3 UNIT.CONV.
identical with 3.2.3
2.0 TEST
2.1 HARDWARE
2.1.1 MASTER
Master hardware test.
2.1.2 DISPLAY
Display hardware test.
2.1.3 STATUS
Status information for Service
2.2 CUR.OUTP.I
2.2.1 VALUE I
Value display
Display of actual value of the current
output.
2.2.2 TEST I
Select 2 mA/4 mA/6 mA/...
... 20 mA/22 mA
Output of selected value to the current
output. With safety query.
2.4 FIRMWARE
2.4.1 MASTER
Display
Display of master firmware version.
2.4.2 DISPLAY
Display
Display of display firmware version.
3.0 INSTALL.
3.1 BASIS.PARAM
3.1.1 TANKHEIGHT
Select unit m/cm/mm/
inch/Ft
Enter
0.50 ... 20.00 [m]
Enter tank height (see explanatory
notes).
The unit entered here is also used for
all other length entries.
3.1.2 BLOCKDIST
Enter
0.10 [m] ... tank height
Enter block distance = non-measurable
range below bottom edge of flange (see
explanatory notes).
3.1.3 ANTENNA
Select STANDARD
WAVE-STICK
Select antenna type. WAVE-STICK for
all Wave-Stick versions, except type
"SW" for stillwells. All other =
STANDARD.
3.1.4 ANT.EXTENS.
Enter 0.00 [m] ... tank height Enter length of antenna extension.
3.1.5 DIST.PIECE
Enter 0 ... 2000 [mm] Enter length of distance piece above
flange (high temperature version =
120
mm).
3.1.6 STILLWELL
Select NO / YES
If “YES“: enter 25 ... 200 [mm]
Selection: without or with still well.
With still well: enter inside diameter in
[mm] (compensates different wave
speeds in still wells)
3.1.7 REF.OFFSET
Enter -10.00...0...+10.00 [m] Reference offset is added to measured
distance values.
3.1.8 TB.OFFSET
Enter -100.00...0...+100.00 [m] Tank bottom offset is added to
measured level values.
3.2 DISPLAY
3.2.1 FCT.DISP
Select LEVEL
DISTANCE
CONVERSION
Select function of display
(value to be displayed).
(see also explanatory notes)
3.2.2 UNIT.LENGTH
Select m/cm/mm/
inch/Ft/
PERCENT/BARGRAPH
Select unit for length value to be
displayed (only for level and distance).
3.2.3 UNIT.CONV.
Select m3/l(Liter)/US Gal/
GB Gal/Ft3/bbl/PERCENT/
BARGRAPH/USER UNIT
Select unit for conversion value to be
displayed (“volume table“).
(see explanatory notes)
3.2.4 USER UNIT
Text entry
10 characters
Enter user-defined unit for the
conversion table.
3.2.5 ERROR MSG.
Select NO/YES Select whether error messages to be
shown in display.