8.1 NAMUR NE 107 Event Group(s)

Modbus Input Register

39004

39005

Byte 0

Byte 1

Byte 2

Byte 3

Byte

Bit

Status
signal

Event group

3

7

-

reserved

6

-

reserved

5

-

reserved

4

-

reserved

3

-

reserved

2

-

reserved

1

I

Electr: Operation Info

0

-

reserved

2

7

-

reserved

6

S

Electr: IO Connection

1

5

S

Proc: Empty Pipe

1

4

S

Proc: Signal Lost

1

3

S

Proc: Signal Unreliable

1

2

S

Config: Totaliser

1

1

-

reserved

0

I

Electr: Power Failure

1

1

7

S

Sensor

6

S

Electronics

5

S

Configuration

4

S

Process

3

M

Sensor

2

M

Electronics

1

M

Configuration

0

M

Process

0

7

F

Sensor

6

F

Electronics

5

F

Configuration

4

F

Process

3

C

Sensor

2

C

Electronics

1

C

Configuration

0

C

Process

1 Those event groups can be mapped to any status signals.