Submenu 3.06.00 Digital input
Function 3.06.01 Function of digital input
The digital input terminal is the same as the current output terminal. Therefore, when the digital input function is
selected, the function of the current output (see Function 3.04.01) needs to be set to OFF and the current output range
has to be set to 0-20mA (see Function 3.04.03).
The digital input can programmed for the following functions:
• OFF switched off, no function
• RST ERROR reset error messages, see also Function 0.00.02 RST ERR
Submenu 3.07.00 User data
Function 3.07.01 Through 3.07.04 Language for display texts / Entry code for setting mode / Code 1 / Tag name
setting
Function 3.07.05 through 3.07.07 User-defined unit for volume flow rate
Instead of choosing from pre-defined units for the volume flow as in Function 3.01.01 FULL SCALE, a user-defined unit
can be programmed. This unit is to be defined as a volume unit per time unit. In Function 3.07.05 UNIT TEXT the text
can be defined, in Function 3.07.06 UNIT VOL the amount of volume units that will fit in one m³ must be programmed,
and in Function 3.07.07 UNIT TIME the amount of seconds that will fit in a time unit must be programmed.
Example: to program barrels per day, program in Function 3.07.06 6,289 (= 1/0,159) and in 3.07.07 8,640E4
(=24*60*60).
3.11.5 Main menu 4.00.00
Parameter error
For description see under main menu 0.00.00.