Parameter / Variable
(short description)

Name

Explanation

Relative
address

Absolute

address,

non-

Modicon

Absolute

address,

Modicon-

comp.

Units

Low Flow cutoff Threshold

Low_Flowcut_-
ThresHold

Hysteresis preventing frequent on/off switching of low flow
cut-off

22

7522

7544-7545

(2 regs)

%

Alarm configuration

Parameter / Variable
(short description)

Name

Explanation

Relative
address

Absolute

address,

non-

Modicon

Absolute

address,

Modicon-

comp.

Units

Allowed Deviation SOS per
channel on SOS average Pipe

SOSDev

Defines alarm limit for deviation of measured SOS of any
acoustic path from average value of all paths (all SoS values
calculated with mach-correction).

23

7523

7546-7547

(2 regs)

m/s

Input Temperature Proces:
LimitHigh

T_LimitHigh

Upper limit for process temperature measurement.

24

7524

7548-7549

(2 regs)

°C

Input Temperature Proces:
LimitLow

T_LimitLow

Lower limit for process temperature measurement.

25

7525

7550-7551

(2 regs)

°C

Viscosity configuration

Parameter / Variable
(short description)

Name

Explanation

Relative
address

Absolute

address,

non-

Modicon

Absolute

address,

Modicon-

comp.

Units

Dynamic Viscosity at
Reference Temperature

VD_Reference_Visc

Input value of dynamic viscosity, used as base value to correct
reference viscosity to actual viscosity at process temperature
and pressure.

26

7526

7552-7553

(2 regs)

cP

Reference Density

D_Reference_Dens

Input value of density, used as base value to correct reference
density to actual density at process temperature and pressure.

27

7527

7554-7555

(2 regs)

kg/m

3