KROHNE OPTISONIC V6 Modbus User Manual

Page 19

background image


2011-07-19

OPTISONIC_V6_Modbus_6.doc

19/29

K

R

O

H

N

E

C

T

P

ro

d

u

c

ts

Parameter / Variable
(short description)

Register Name

Bit Bit Name

Explanation

Relative
address

Absolute

address,

non-

Modicon

Absolute

address,

Modicon-

comp.

Units

Channel 2 Unreliable

Alarm&Status
Channel_2

0 A Ch_Unreliable

Alarm flag indicating path error (channel
2): channel unreliable.

3

5003

5006-5007

(2 regs)

[status]

Channel 2 Down

Alarm&Status
Channel_2

1 A Ch_Down

Alarm flag indicating path error (channel
2): channel down

3

5003

5006-5007

(2 regs)

[status]

Channel 2 Down: SoS
Deviation too large

Alarm&Status
Channel_2

2 A Ch_Deviation_SOS

Alarm flag indicating path error (channel
2): SOS deviation too large.

3

5003

5006-5007

(2 regs)

[status]

Channel 2 Down: Signal
lost

Alarm&Status
Channel_2

3 A Ch_Signal_Lost

Alarm flag indicating path failure
(channel 2): signal lost

3

5003

5006-5007

(2 regs)

[status]

Channel 3 Unreliable

Alarm&Status
Channel_3

0 A Ch_Unreliable

Alarm flag indicating path error (channel
3): channel unreliable.

4

5004

5008-5009

(2 regs)

[status]

Channel 3 Down

Alarm&Status
Channel_3

1 A Ch_Down

Alarm flag indicating path error (channel
3): channel down.

4

5004

5008-5009

(2 regs)

[status]

Channel 3 Down: SoS
Deviation too large

Alarm&Status
Channel_3

2 A Ch_Deviation_SOS

Alarm flag indicating path error (channel
3): SOS deviation too large.

4

5004

5008-5009

(2 regs)

[status]

Channel 3 Down: Signal
lost

Alarm&Status
Channel_3

3 A Ch_Signal_Lost

Alarm flag indicating path failure
(channel 3): signal lost.

4

5004

5008-5009

(2 regs)

[status]

Reserved

Reserved

-

Reserved

Reserved

5-7

5005-5007

(3 regs)

5010-5015

(6 regs)

-

Process Temperature
Out of range

Alarm Inputs

0 A_Temperature_OOR

Alarm flag, measured body temperature
is out of range.

8

5008

5016-5017

(2 regs)

[status]

Process temperature:
Override value used

Alarm Inputs

1 A_Temperature_OVR

Status/alarm flag indicating manual
input of temperature value overrides
measured temperature (process
temperature input); will appear in case
alarm parameter nr 6 set to enabled and
Override Mode (User Control) set to
enabled (mode 1 or 2); Mode 3 will not
generate an alarm.

8

5008

5016-5017

(2 regs)

[status]