MODBUS REGISTER MAPPING
Registers are mapped to specific address ranges according to both data and register type:
Data type
Register type
Read command(s)
Write command(s)
Address range
Input Register
4
n.a.
3000..3499
Integer (16 bit)
Holding Register
3
6, 16
3500..3999
Input Register
4
n.a.
5000..5499
Long integer (32 bit)
Holding Register
3
6, 16
5500..5999
Input Register
4
n.a.
6000..6499
Double (64 bit)
Holding Register
3
6, 16
6500..6999
Input Register
4
n.a.
7000..7499
Float (32 bit)
Holding Register
3
6, 16
7500..7999
Input Register
4
n.a.
8000..8499
Long long (64 bit)
Holding Register
3
6, 16
8500..8999
Note: The relative addresses listed in the tables below are addresses relative to the starting address of the designated register group.
8.1
Input Registers (read-only): Integer (16-bit); address range 3000-3499
Parameter / Variable
(short description)
Name
Explanation
Relative
address
Absolute
address,
non-
Modicon
Absolute
address,
Modicon-
comp.
Units
Test register
TestRegister uint16
Register reserved for testing communications and protocol
handling with this type of register, without affecting the operation
of the flow meter.
0
3000
3000-3001
(2 regs)
-