6 Troubleshooting

This chapter documents the possible errors that can occur. They are ordered by error parameter or block.

Normally, the errors don’t occur solely, but in conjunction with other errors, described here.

6.1 BLOCK_ERROR

Each block has a parameter BLOCK_ERR, that reflects possible problems with the block. The following

describes these possible problems and the necessary action to be taken by the user.

6.1.1 Resource

Block

The following table lists the block errors documented by the Resource Block:

Error Code

Description

Action

Out of Service

Target mode is set to ‘Out of
Service (OOS)’

If Automatic is the desires target mode, set
MODE_BLK target to ‘Automatic (Auto)’

Power-up

Power failure of measurement
electronics (NOTE: Not the
bus power!)

This requires an action at the device’s display:
Quit the ‘ERROR QUIT’ menu at the device’s display.
Refer to the ‘Installation and operating instructions,
Signal converters for electromagnetic flowmeters’
manual.
Note: No counting during power failure.

Device needs
Maintenance

Fatal error of the
measurement electronics

Replace signal converter or contact KROHNE service.

Memory Failure

Device memory failure

Replace signal converter or contact KROHNE service.

Input Failure

AD converter error.

Replace signal converter or contact KROHNE service.

Other

Other hardware problem.

Replace signal converter or contact KROHNE service.

6.1.2 Transducer

Block

The following table lists the block errors documented by the Transducer Block:

Error Code

Description

Action

Out of Service

Target mode is set to ‘Out of
Service (OOS)’

If Automatic is the desired target mode, set
MODE_BLK target to ‘Automatic (Auto)’

Communication problem
between FF module and
measurement module

Replace signal converter or contact
KROHNE service.

Device Needs Maintenance Now

AD converter error.

Replace signal converter or contact
KROHNE service.