Supplementary Documentation

Page 30 of 44

IFC090, IFC090 i with FF

IFC090-FF Configuration

IFC090 FF 01/2006

KROHNE Messtechnik GmbH & Co. KG · Ludwig-Krohne-Str. 5 ‚ D-47058 Duisburg

Tel.: 0203-301 309 ‚ Fax: 0203-301389 · E-mail: [email protected]

Since most of the Transducer Block parameters are depending on device settings which are configurable over

the device’s display only, there are not many what the user has to configure.

5.2.1 Transducer Block Mode Handling

As in other blocks the mode handling in the Transducer Blocks can be controlled by the parameter MODE_BLK.

The Transducer Block supports the following modes:

• Automatic

(AUTO),

• Manual

(MAN),

and

• Out of Service (OOS)

In Automatic mode, the Transducer operates in its standard way and delivers its measurement value and status

as parameter PRIMARY_VALUE via channel 1 to the Function Blocks4 (if any).

Different from the Automatic mode, in Manual mode the Transducer Block freezes its measurement value and

sets its status to Uncertain:NonSpecific Constant.

To stop the complete operation of the Transducer Block, set its mode to Out of Service. In this mode, the

Transducer Block freezes its measurement value to the last one obtained in Automatic mode and sets its status

to BAD:OutOfService:NonSpecific.

If the block is in Out of Service mode, this is also indicated by its BLOCK_ERR parameter.

5.2.2 IFC090-FF Zero Point Calibration

The Transducer Block allows a calibration of the devices zero point.

To do this, the number of calibration cycles has to be specified first by setting parameter

CYCLES_ZEROPOINT_CAL (default value is 250).

To start the zero point calibration, parameter CAL_ZEROPOINT has to be set to a value different to zero (0).

5.3

Analog Input Block Configuration

The Analog Input block is one of the 3 Function Blocks supported by the IFC090-FF. It can be used to process

the measurement value obtained from the Transducer Block in a user defined way and to deliver it to the control

system. To this end, there are some parameters in the Analog Input Block, that can be configured to get a

measurement value quality as desired by the user.

Analog Input Block Mode Handling

By selecting the operation mode in parameter MODE_BLK, the operator is able to control the activities of the

Analog Input block. The following lists the available modes and meanings:

4

Normally, this is the Analog Input block, but it has to be configured to process the channel value.