KROHNE IFC 090 i Converter FOUNDATION FIELDBUS User Manual

Page 25

background image

Supplementary Documentation

Page 25 of 44

IFC090, IFC090 i with FF

IFC090-FF Block Description

IFC090 FF 01/2006

KROHNE Messtechnik GmbH & Co. KG · Ludwig-Krohne-Str. 5 ‚ D-47058 Duisburg

Tel.: 0203-301 309 ‚ Fax: 0203-301389 · E-mail: [email protected]

Parameter

Access

Description

OUT_PTRIP R/W

Second discrete output. OUT_PTRIP can be used within a control system, to
get a discrete indication, that a specified value of totalization is reached (e.g.
as indication to start closing a valve). The specified value to reach can be set
in parameter PRE_TRIP.
NOTE:
If the totalization reaches PRE_TRIP, OUT_PTRIP is set to 255 (0xFF).
see also: PRE_TRIP, OUT_TRIP

OUT_RANGE R

Display scaling of the output OUT. It has no effect on the block and is used
by downstream blocks or control system to get the unit of the totalization.

OUT_TRIP R/W

Second discrete output. OUT_TRIP can be used within a control system, to
get a discrete indication, that the specified value of totalization for resetting
(automatic reset is selected) is reached. The specified value to reach can be
set in parameter TOTAL_SP.

see also: TOTAL_SP, OUT_PTRIP

OUTAGE_LIM R/W

Maximum tolerable time for power failure. Not used by the IFC090-FF

PCT_INCL R

Percentage of BAD and Uncertain net flow values used in conjunction with
GOOD_LIM and UNCERT_LIM to determine the status of the output value
OUT. It is calculated by the following equation:

PCT_INCL = 100 * (1 - (rtotal / atotal),
where rtotal is the portion of BAD and Uncertain net flows and atotal the
absolute value of all net flows.

see also: GOOD_LIM, UNCERT_LIM

PRE_TRIP R/W

When integration is counting up (see INTEG_TYPE) and the totalization
value equals or exceeds (TOTAL_SP - PRE_TRIP) then the discrete output
OUT_PTRIP is set to 0xFF.

If counting down and the value of OUT is equal to or less than PRE_TRIP,
the discrete output OUT_PTRIP is set to 0xFF.

see also: OUT_PTRIP

PULSE_VAL1 R/W

PULSE_VAL1 specifies the factor by witch IN_1 is to be multiplied if IN_1 is
used as input of accumulated pulses (i.e. ‘Input 1 accumulate’ is set in
INTEG_OPTS). In this respect, IN_1 will be converted according to the
following equation:
IN_1 = IN_1 * PULSE_VAL1

PULSE_VAL2 R/W

PULSE_VAL2 specifies the factor by witch IN_2 is to be multiplied if IN_2 is
used as input of accumulated pulses (i.e. ‘Input 1 accumulate’ is set in
INTEG_OPTS). In this respect, IN_2 will be converted according to the
following equation:
IN_2 = IN_2 * PULSE_VAL2

RESET_CONFIRM R/W

RESET_CONFIRM can be used by control systems to confirm a reset event
report if ‘Confirm reset’ is set in INTEG_OPTS.

RESET_IN R/W

RESET_IN can be used by control systems to reset the totalization by an
external signal. By setting 'value' to 'Reset' (0x01) and a status of
GoodNC:NS:NL, the integrator will be reset as if OP_CMD_INT was set to
'Reset'.

see also: OP_CMD_INT, INTEG_TYPE