Illegal character

If any invalid character is entered.

Max range failure occurred writing level
20mA.Restore device value

It appears if entered Value for 20mA is
out of range.

Method is currently invalid

It appears if access right is not


5

HART® Communicator 375 (HC375)

5.1 Offline

Restriction

In order to transfer an Offline configuration to the device the Service parameter “Supervisor

Password Enable” (C.5.2.0)

must be set to “NO”.

In case this parameter has got the value “YES” the configuration is not transferred successfully to the

device even if we don’t see any error messages!

5.2

Save Device Parameters

ATTENTION

: This is

a very important method

.

Each time the device configuration is modified (after sending new values) it is necessary to execute this

method. Otherwise the modifications will not be taking into account.

This method is only accessible in case the supervisor or service password method has been executed.