beautypg.com

KROHNE OPTIWAVE Hart User Manual

Page 3

background image

User Guide for Optiwave (FMCW) DD of AMS

Dev Rev-01, DD Rev-02


© 2006 KROHNE SAS 26103 Romans (France)

Page 3 of 34

1

HART® Transmitter Revisions and Instrument Firmware

1.1 Device Revision

The Optiwave HART® transmitter has only one revision: Device revision 1.

1.2 DD Revision


Optiwave 7300C has the DD revision 2.
DD is tested with AMS 9.0.

2

Installation

of

DLL

in

AMS

Refer to the AMS help to install the device (Optiwave 7300C) into an AMS System.

3 Menu

3.1 Access

Rights

3.1.1 Password

protection implementation

There will be two user login, Supervisor & Service which is implemented in
menu. By default, Supervisor can see & edit all parameters except service parameter. After service
person is logged in he can see & edit all the parameters including the service parameters and
tables.

Password can be numeric digits from 0-9. There may be maximum six digits password. As we
can’t store the password directly in AMS, we are validating the password in AMS by reading the
password from device. Password setting facility is not given from AMS to avoid conflicts to know
the password to login from HMI. After validation it will give following messages “Supervisor
Password OK” or “Service Password OK” as per the login. On clicking the Access Rights on the
main menu, two submenus appear as Supervisor and Service

.