9.3 Characteristics for the device safety function
If it is necessary to use the device in a low demand mode (as specified in document [N2]), refer to
the table below. For example, the device can be used to give a warning if an error signal occurs.
The table shows the change of PFD
AVG
with a T[Proof] between 1 to 10 years:
For more data, refer to
Proof tests
on page 19.
Version
Non-Ex / Ex i
Ex d
Firmware version
Converter: 1.06.02; Sensor: 1.21.02
Board version
Converter: 4000678801B;
Sensor: 4000786001B
Converter: 4000678801B;
Sensor: 4000786001B
Ex d barrier: 4000633801A
Systematic capability
2
2
Architecture
1oo1D (daily auto-diagnostic checks)
PFH
6.50Ч10
-8
1.08Ч10
-7
SFF
94%
91.7%
λ
SD
3.46Ч10
-8
1.09Ч10
-7
λ
SU
4.71Ч10
-7
4.71Ч10
-7
λ
DD
5.71Ч10
-7
6.81Ч10
-7
λ
DU
6.50Ч10
-8
1.08Ч10
-7
DC
D
90%
86%
MTBF
99 years
83 years
Year:
1
2
3
4
5
6
7
8
9
10
PFD
AVG
(Non-Ex / Ex i)
2.88
Ч10
-4
5.74
Ч10
-4
8.59
Ч10
-4
1.14
Ч10
-3
1.43
Ч10
-3
1.71
Ч10
-3
2.00
Ч10
-3
2.28
Ч10
-3
2.56
Ч10
-3
2.85
Ч10
-3
PFD
AVG
(Ex d)
4.78
Ч10
-4
9.52
Ч10
-4
1.43
Ч10
-3
1.90
Ч10
-3
2.37
Ч10
-3
2.84
Ч10
-3
3.32
Ч10
-3
3.79
Ч10
-3
4.26
Ч10
-3
4.73
Ч10
-3