7

OPERATION

16

OPTIFLEX 2200 C

www.krohne.com

01/2013 - 4000738603 - AD SIL OPTIFLEX 2200 R03 en

7.5 User parameters

7.5.1 Limits for supervisor menu functions related to probe configuration

INFORMATION!
If you change a parameter set in one or more of the menu items that follow, this will have an
effect on the safety function.

WARNING!
If the device was delivered without a probe, then calibrate the device to make sure that the safety
function operates correctly. For more data, refer to Calibration procedure on page 22

.

CAUTION!
This section gives data on the modification of a small number of parameters in the 2.0.0
SUPERVISOR menu. If it is necessary to change parameters in the 3.0.0 SERVICE menu or the
4.0.0 MASTER menu, contact your supplier.

If you change the values of one or more of the parameters given in the "User parameters"
section, this can have an unwanted effect on the safety function. Do a check of the safety
function after you change a parameter.

INFORMATION!
Safety function check

Safety function check

Safety function check

Safety function check
Make sure that the 4...20mA measurement range is correctly calibrated.

LEGAL NOTICE!
The manufacturer declines all responsibility for the correct operation of the safety function if
these parameters in the 3.0.0 SERVICE or 4.0.0 MASTER menus are changed by the customer.

Menu

No.

Function

Function description

Selection list

Default value

and comments

2.3.3

PROBE LENGTH

Probe length is the distance

from the flange face / thread

stop of the device to the

bottom end of the probe

(including counterweight for

cable versions).

min:

2.3.4 BLOC. DIST. +

3.1.1 COUNTERWEIGHT

max.:

40 m / 131 ft

Default value

agrees with the

customer

order.

2.5.7

MEAS. THRESH.

Measurement threshold. If it is

difficult to identify the level

signal (for example: too many

parasite signals), you can

increase the threshold. A

threshold of 1000 is equivalent

to the amplitude of the

measurement pulse. A

threshold of 100 is equivalent

to 10% of the amplitude of the

measurement pulse. For more

data, refer to “Operation” in

the handbook (document

[N1]).

min-max: 0…1000

Default value

depends on the

ε

r

of the liquid

or solids in the

tank and the

probe type.