COMMISSIONING / OPERATION
10
OPTIFLEX 2200 C
www.krohne.com
10/2013 - 4003066801 - MA OPTIFLEX2200C-PA-R01-en-
4.2 GSD files
The GSD file contains information that will be needed for configuration of the PROFIBUS DP
communication network. Supplementary files (e.g. ___.bmp and ___.dib) contain icons which will
represent the PROFIBUS devices in the view of the bus configuration system/master system. The
files must be loaded into the configuration program before you connect the device to the
network. Follow the instructions in the manual of the host supplier when installing GSD file and
supplementary files.
The GSD files of all KROHNE devices with PROFIBUS PA interface are available at the KROHNE
internet site for download.
4.3 Ident. Number
Manufacturer specific Ident. Number (4550hex)
Manufacturer specific Ident. Number (4550hex)
Manufacturer specific Ident. Number (4550hex)
Manufacturer specific Ident. Number (4550hex)
This setting gives a complete set of operations that can be run on the device. All Functions
Blocks (4 AI-FB) are used for cyclic data transfer. Device-specific diagnosis data is transferred in
addition to the Profile diagnosis.
Cyclic layout:
It is necessary to use GSD file KR014550.GSD in this mode. It is possible to use this file for all
types of PROFIBUS DP/PA segment couplers.
INFORMATION!
If it is supported by the host configuration tool the device entry for the level meter will be located
within the slave family
“
PROFIBUS PA
”
.
Slot
Function Block
Valid GSD Modules
1
AI-FB
Empty Module
AI: Out
INFORMATION!
If a different GSD file is used in the PROFIBUS master system, it is not possibe to transfer cyclic
data.