Technical data – KROHNE MFC 300 Modbus User Manual

Page 4

background image

2

TECHNICAL DATA

4

MFC 300

www.krohne.com

11/2009 - 4000744801 - AD Modbus MFC 300 R01 en

Technical data

2.1 General technical data

2.2 Technical data of the Modbus interface (acc. to EIA standards)

Interface

RS485, galvanically isolated

Baud rate

1200, 2400, 4800, 9600, 19200, 38400, 57600 or 115200

Protocol

Modbus RTU (available as a separate document on request)

Maximum participants on bus

32 per line, master included (may be extended by repeaters)

Coding

NRZ bit coding

Address range

Modbus: 1...247

Transmission procedure

Half duplex, asynchronous

Bus access

Master / slave

Cable

Screened twisted pair

Distances

Maximum 1.2 km / 3937 ft without repeater (dependant on

baud rate and cable specifications)

Kind of signal transmission

Differential, 2-wire topology

Maximum number of

transmitter/receivers

32

Voltage range on converter input

-7...+12 V

Maximum voltage on converter output

5 V

Minimum voltage on driver output, max.

load

U

diff

> 1.5 V

Maximum input current (off state)

-20...+20 μA

Receiver input voltage

-7...+12 V

Sensitivity of the receiver

-200...+200 mV

Receiver input resistance

> 12 kΩ

Short circuit current

< 250 mA

Termination / polarization resistors

(if activated by the jumpers X5/X6)

120 Ω / 560 Ω