Manual OPTISENS PAC 050

19

OPTISENS PAC 050

5.2 P / PI controller as impulse-frequency controller

Main menu

.

.

Set points and

controller version

Set points

Setpoint S1

You can choose different

.

7.50 pH

controller versions for S1

.

P range S1

and S2

.

0.20

pH

Integral time S1

000

sec

Set points S2

6.50

pH

P range S2

Controller settings

0.20 pH

Pulse-Freq. S1

Integral Time S2

00*100/4

000 sec.

Pulse-Freq. S2

00*100/h

Basic settings

Direction

S1

Basic settings

.

Raise

.

Direction

S2

Contr.

settings

Lower

For an impulse-frequency controller you have to set the following parameters:

1) Set points S1 and S2
S1 refers to relay 1, S2 refers to relay 2.

2) P range and integral action time for S1 and S2
Adjust a P range > 0. For a P controller set integral time = 0, for a PI controller set an integral time > 0.

3) The acting direction for S1 and S2
Select „raise“ if the dosage raises the measured value.

Select „lower“ if the dosage lowers the measured value.

4) Pulse-frequencies for S1 and S2
Enter the maximum pulse-frequency that corresponds to 100% dosage.

5.3 P / PI controller as pulse-pause controller


Main menu

.

.

Set points and

controller versions

Set points

Set point S1

You can choose

.

7.50

pH

Different controller

.

P range S1

Controller Settings Versions for S1+S2

.

0.20 pH

Pulse-Freq. S1

.

Integral time S1

00*100/h

000 sec

Pulse-Freq. S.2

Set point S2

00*100/h

6.50 pH

Direction S1

P range S2

Raise

0.20 pH

Direction S2

Integral time S2

Lower

000

sec.

.

.

Basic settings

Pulse+Pause

The pulse+pause time

Basic settings

.

10

sec

must be at least twice

.

Least Pulse

as long as the least

Contr.

settings

0.1 sec

pulse time