beautypg.com

KROHNE OPTISENS PAC 050 EN User Manual

Page 18

background image

Manual OPTISENS PAC 050

OPTISENS PAC 050 18


You can choose between three different controller versions:

ON/OFF controller
The ON/OFF controller switches ON if the measured value exceeds the set point and OFF if it drops back

below it or vice versa. Dosage is always carried out with 100% (ON) or 0% (OFF). The parameter for an
ON/OFF controller is the hysteresis.

P controller
The P controller or proportional controller reduces the dosage in the vicinity of the set point proportional to

the control deviation. This is easily achieved if the analog output is used as steady control output. If the

relays are used, the proportional reduction is achieved by either reducing the switch frequency (Impulse-

frequency controller) or reducing the time within a given period of time in which the relay is ON (pulse-pause
controller).

The parameters for a P controller are the P range and the impulse- frequency or the pulse+ pause time and

the minimum pulse.

PI controller
The PI controller is a P controller with an additional I function. Adjustments and parameters are the same as
for a P controller. Additionally the integral action time has to be adjusted which determines the I function.

The I function eliminates the P controller’s disadvantage of a remaining steady-state deviation.

5.1 ON/OFF controller


Main menu

.

.

Set points and

controller version

Set points

Set point S1

You can choose different

.

7.50 pH

controller versions for S1

.

P range S1

and S2

.

0.20

pH

Integral Time S1

000

sec.

Set point S2

6.50

pH

P range S2

Controller settings

0.20

pH

.

Integral Time S2

.

000 sec.

Direction S1

raise

Basic settings

Direction

S2

Basic settings

.

Lower

.

Hysteresis

Contr.

settings

0.01 pH

For an ON/OFF controller you have to set the following parameters:

1) Set points S1 and S2
Set point S1 refers to relay 1, set point S2 refers to relay 2.

2) P range and integral action time for S1 and S2
For an ON/OFF controller set P range = 0 and integral time = 0.

3) Acting direction for S1 and S2
Select “raise“ if the dosage raises the measured value.
Select “lower“ if the dosage lowers the measured value.

4) Optionally a hysteresis
The hysteresis prevents fast switching in the vicinity of the set point. If hysteresis is activated (by setting a
value > 0) the relay switches only when the set point is exceeded by half the hysteresis.