OPTISENS AAC 050

9.

Technical data

9.1

Technical data


Feature

AC 050 P

AC 050 W

Version

panel-type converter

wall-mounting enclosure

Dimensions (w x h x d)

96 x 96 x 127 mm / 3.8 x 3.8 x 5”

165 x 160 x 80 mm / 6.5 x 6.3 x 3.1”

Weight

0.8 kg / 1.8 lbs

1.0 kg / 2.2 lbs

Terminals

screw terminals max. 1.5 mm

2

Protection class

IP 54 (front), IP 30 (housing)

IP 65

Power supply

85...265 V AC (48...63 Hz) / DC;
option: 18...50 V AC (48…63 Hz) / DC

Internal fuse

none

230 V: 63 mA slow
110 V: 125 mA slow
24 V: 800 mA semi-slow

Power consumption

10 VA

10 VA

Display

LCD, 2-line, 2x16 characters, illuminated background ,
measured value and temperature with dimensions indication of relay
status

Current outputs

2 x 0/4...20 mA, galvanically isolated, max. loading 500 Ohm

Interface (option)

RS485, Baud rate 9600, data format 8Bit, 1 Start and 1 Stop bit

Controller

ON/OFF controller with hysteresis, P or PI controller as Pulse- Pause- or
Impulse-frequency controller, steady controller, bidirectional PI control
action, adjustable onset-delay, dosage control function, manual operation
of the relays, controller stop via external switch or level sensor (lack-of-
water sensor)

Set points

2 set points adjustable within the measuring range

Alarm function

with min. and max. limit and turn-on delay

Contact rating

6 A/ 250 V, max. 550 VA resistive load (with RC protective circuit)

Operation temperature

0…+50°C / 32…+120°F

Storage temperature

-20…+65°C / -5…+150°F

Humidity

max. 90% at 40°C /105°F non-condensing