Manual OPTISENS AAC 050

21

OPTISENS AAC 050

5.4

Activation and deactivation of the controller

The controller is activated and deactivated from the main display without any menus. Press key

to switch

from Manual Mode (controller OFF) to Automatic Mode (controller ON) and vice versa. The actual mode is
indicated in the display.

CAUTION

Make sure that the controller is deactivated before connecting dosing pumps or other actuators!


Main menu

.

.

Basic settings

Basic settings

.

.

Turn-on delay

Turn-on delay

Turn-on delay

OFF

ON

Turn-on delay

180 s

5.5

Turn-on delay

Set a delay time which has to pass before the controller is activated after start-up or power interrupt. This
allows the measurement to settle and prevents inappropriate dosage of chemicals.

5.6

External controller stop

You can activate or deactivate the controller with an external switch by using the digital input. This feature
requires no settings or adjustments. If the digital input is short- circuited, the controller stops, and the
message „external controller stop“ appears in the display.

NOTE

This feature can also be used as lack-of water indication. Just connect a level sensor to the digital input.