CAPAFLUX IFM 5080 K/CAP-EEx and CAPAFLUX IFM 5080 K/CAP i-EEx

11

Terminal compartment MODIS version IFC 090 / CAP i-EEx

Sticker with handling information
for insulating cover plate

Sticker indicating the intrinsically
safe signal in-/output circuits

Insulating cover plate


The PE (or FE) conductor must be connected to the press-fitted M5 clamp terminal marked inside the
terminal compartment. This conductor must be guided through the rectangular opening in the metal
dividing plate that separates the non-intrinsically safe power supply terminals from the intrinsically safe
signal in-/output terminals.

2.6 Connection

diagrams

MODIS

Sect. 2.3 shows the block diagram of the EEx electromagnetic compact flowmeter. The power supply
(terminals 1L

Ÿ

, 0L

Ÿ

) is connected via cable B. The PE terminal must be connected to the protective

ground conductor of the mains supply.

The IFC 090 / CAP i-EEx electronics unit is provided with intrinsically safe signal in-/output circuits due
to the installed pair of MODIS modules in accordance with the table below.