beautypg.com

KROHNE CAPAFLUX EEx-ATEX EN User Manual

Page 10

background image

CAPAFLUX IFM 5080 K/CAP-EEx and CAPAFLUX IFM 5080 K/CAP i-EEx

10

2.5

MODIS version IFC 090 / CAP i-EEx electronics unit

The field cables of the non-intrinsically safe power supply and the intrinsically safe, category "ia" signal
outputs enter the terminal compartment of the IFC 090 / CAP i-EEx signal converter unit via two
separate entrances. To connect external devices to the intrinsically safe signal output terminals, the
wiring requirements for their type of protection as well as of the compartment (standard: increased
safety "e", optional: flameproof enclosure "d") must be conform to the international or national standard
involved (e.g. EN 60079-14).

Terminal arrangement in terminal compartment

Metal dividing
plate IS / non-IS
terminals

NC 1LŸ 0LŸ 24

Vac/dc

L

N

100…240

Vac

PE

Protective Earth terminal

Connecting terminals

for intrinsically safe

signal in-/outputs

Connecting
terminals for
non-intrinsically
safe power supply

Cable entrance for

non-intrinsically
safe power supply
cable

Cable entrance for

intrinsically safe
signal cable

NC = not connected

* * * *


The non-intrinsically safe terminals for connection of the power supply (1L

Ÿ

and 0L

Ÿ

) must be

connected according to the relevant standard code of practice for electrical apparatus intended for use
in potentially hazardous locations, type of protection Increased Safety "e" or type of protection
Flameproof Enclosure "d", depending on the type of protection of the terminal compartment of the signal
converter housing.

To gain access to the connection terminals of the power supply, the half-circular cover plate of
insulating material must be slightly lifted at one end and then rotated downwards, see the instruction on
the cover plate. After connection of the power supply cable, the half-circular cover plate must be
restored into its original position, so that the minimum clearances and creepage distances towards the
intrinsically safe signal in-/output terminals are maintained.

For details, see diagram on terminals compartment MODIS on next page.