Installation instructions VARIFLUX 6000

7

5

Installation in the pipeline


Installation material not included, to be provided by customer (stud bolts,

nuts, gaskets, etc.)


Pipe connections, operating temperature and pressure:

refer to tables on “Limits” in Section 6.


Fitting dimension

see Sect. 12 “Dimensions and weights”;


High-temperature pipelines

Where process temperatures exceed 100 °C/212 °F, provide for facilities to compensate for
longitudinal expansion on heat-up of the pipeline.
For short pipelines use resilient gaskets and for long pipelines install flexible pipe elements
(e.g. elbows).



Position of connections

Install flowmeter in line with the pipe axis. Pipe
connections must be parallel to each other, max.
permissible deviation:
L

max

- L

min

0.5 mm

0.02’’


Torques


For flanged instruments
to DIN 11864-2a

Tighten down stud bolts and nuts
with max. torque:
32 Nm ~ 3.2 kpm ~ 23.5 ft x lbf

For all other connections
Tighten down to metal stop.