Electrical connections, 4 grounding and equipotential bonding – KROHNE OPTITEMP TCA Ex EN User Manual

Page 28

background image

4

ELECTRICAL CONNECTIONS

28

OPTITEMP TRA/TCA

www.krohne.com

10/2010 - 4001087001 - Ex AD OPTITEMP TRA/TCA R02 en

4.4 Grounding and equipotential bonding

The manufacturer's measuring insert connections withstand a test voltage of 500 VAC to earth.

DANGER!
In order to prevent injury and material damage, always observe the following points regarding
grounding and equipotential bonding:

Always include the thermometer and its measuring insert as per EN 60079-14 in the
equipotential bonding of the installation site (when installed correctly, the fixing screws
guarantee this).

If the thermometer is not connected to a grounded metal pipe system or a container through
the process connection, you must include it in the equipotential bonding of the explosive area.

The connection for equipotential bonding is via the PA terminals or the process connection.

If there is a cable shield you must ground it according to EN 60079-14. A terminal in the
connection head means that the cable shield can be grounded by the shortest route.