2.7.3 Temperature at process connection (with temperature transmitter)
Maximum permitted temperature at process connection for thermometers with temperature
transmitter in [°C]
Maximum permitted temperature at process connection for thermometers with temperature
transmitter in [°F]
DANGER!
The maximum permitted temperature at the process connection for all industrial thermometers
is T
P
= 400°C / 752ºF. The maximum permitted ambient temperature is T
a
= 85°C / 185°F.
Thermometer models
T
a
= 40ºC
T
a
= 60ºC
T
a
= 75ºC
T
a
= 80ºC
TxA-S11, threaded thermometer, neck pipe length ≤ 80mm
135
107
86
80
TxA-S12/41, threaded thermometer, neck pipe length ≥ 80mm
400
292
133
80
TxA-P10/40, insert thermometer with thermowell TxA-P10,
neck pipe length ≤ 80mm
228
154
98
80
TxA-P10/40, insert thermometer with thermowell, neck pipe
length ≥ 80mm
400
270
127
80
TxA-P14, insert thermometer without thermowell, neck pipe
length ≤ 80mm
228
154
98
80
TxA-P14, insert thermometer without thermowell, neck pipe
length ≥ 80mm
400
270
127
80
TxA-F13/42, flange thermometer, neck pipe length ≥ 80mm
400
319
139
80
Thermometer models
T
a
= 104ºF
T
a
= 140ºF
T
a
= 167ºF
T
a
= 176ºF
TxA-S11, threaded thermometer, neck pipe length ≤ 80mm
275
225
188
176
TxA-S12/41, threaded thermometer, neck pipe length ≥ 80mm
752
558
271
176
TxA-P10/40, insert thermometer with thermowell TxA-P10,
neck pipe length ≤ 80mm
443
309
209
176
TxA-P10/40, insert thermometer with thermowell, neck pipe
length ≥ 80mm
752
518
261
176
TxA-P14, insert thermometer without thermowell, neck pipe
length ≤ 80mm
443
309
209
176
TxA-P14, insert thermometer without thermowell, neck pipe
length ≥ 80mm
752
518
261
176
TxA-F13/42, flange thermometer, neck pipe length ≥ 80mm
752
607
283
176