6.3 TT 60 R specifications
6.3.1 Technical data
Designation
Designation
Designation
Designation
Value
Value
Value
Value
Input
Input
Input
Input
Pt10, Pt50, Pt100, Pt200,
Pt500, Pt1000
-200...+850°C
Ni50, Ni100, Ni120, Ni1000
-200...+250°C
Potentiometer
0...4000
Ω
Thermocouples
Types: B, C, D, E, G, J, K, L, N, R, S,
T, U
Voltage
-10...+1000 mV
Redundant channels and
Redundant channels and
Redundant channels and
Redundant channels and
arithmetic functions
arithmetic functions
arithmetic functions
arithmetic functions
Differential
channel 1 - channel 2 or
channel 2 - channel 1
Average value
0.5 x (channel 1 + channel 2)
Average value with
redundancy
0.5 x (channel 1 + channel 2),
channel 1 or channel 2 if the other
channel fails
Minimum value
Min (channel 1, channel 2)
Maximum value
Max (channel 1, channel 2)
Sensor break function
Sensor break function
Sensor break function
Sensor break function
On / Off
Output
Output
Output
Output
ProfiBus-PA
®
Ambient temperature
Ambient temperature
Ambient temperature
Ambient temperature
-20.. +70°C
Galvanic isolation
Galvanic isolation
Galvanic isolation
Galvanic isolation
1500 VAC, 1 min
Power supply
Power supply
Power supply
Power supply
9...32 VDC
Power consumption
Power consumption
Power consumption
Power consumption
11 mA
Typical accuracy
Typical accuracy
Typical accuracy
Typical accuracy
Pt100
0.1°C
Installation
Installation
Installation
Installation
Rail according to EN 50020, 35 mm
Table 8: TT 60 R specifications