5.2.1
Smart Sense
 
If the appropriate measuring sensors are provided (an additional wire in the sensor), the 
transmitter can continuously monitor the insulation resistance of the sensor, including the 
connection wires. This function (Smart Sense) is possible for resistance thermometers and 
thermocouples. If the insulation resistance is too low, the measured result will be incorrect and 
a message will be generated via ProfiBus. 
This function requires configuration with the "ProfiSoft" software via a PC or via the ProfiBus. 
 
 
5.2.2
Monitoring of sensor aging
 
If a resistance thermometer or a thermocouple with two sensors is used, the TT 60 can be used 
to monitor the aging of the sensor. The transmitter compares the measured values of the two 
sensors. Aging is indicated if the differential between the measured values is too great. In this 
case a message is generated via the ProfiBus. For further information, see the "Profisoft" 
manual. 
 
Action
Action
Action
Action 
To protect the PC connections, they must be closed off using the supplied protection caps 
after configuration has been completed. 
 