Caution – KROHNE OPTITEMP TT 31 R EN User Manual

Page 19

background image

02/2011 – 4000753501 – MA OPTITEMP TT31CR R01 en

www.krohne.com

19

Order number

Comment

Type A (cable)

VI70IPRX0002

ATEX certified

Type C

(adapter)

VI70IPRP0001

--

5.2 General information

CAUTION!

For configuration, the two channel TT 31 R / TT 31 R has on the front side a

separate PC connection for each channel. Connect the cable of the PC configuration

set with the connection of the channel that you wish to configure (see Figure 3).

NOTE!

With the TT 31 R, genuine on-line communication is possible, i.e. access to all functions

during operation. Online communication is only permissible in a safe area.

Ex works setting

The transmitter is shipped with the following settings:

Model

Input

Output

Sensor break

TT 31 R

Pt100, 3-wire, 0…100°C

4…20 mA

On

TT 31 R

Pt100, 3-wire, 0…100°C

4…20 mA

On

Configuration is carried out when the PC is "online", i.e. the transmitter can remain in

operation during configuration.

During configuration, the output is "frozen", i.e. the

transmitter continues to work with the last value.

As soon as configuration has been

completed, the transmitter uses the new parameters.

For configuration, the transmitter must be connected to a supply voltage. If the

transmitter is configured with offline PC cable type D, it is supplied with power via this

cable (see Chapter 5.1.1). The "TempSoft" software is required to configure the

transmitter. The current version is available for downloading on the KROHNE website

http://www.krohne.com/html/dlc/index.shtml.