ELECTRICAL CONNECTIONS

3

23

OPTIWAVE 5200 C/F

www.krohne.com

04/2013 - 4001905802 - AD ATEX OPTIWAVE 5200 R02 en

3.5 Ex ia equipment

3.5.1 How to connect the electrical cables

Cable entries are supplied on customer demand. If you supply the cable entries, this part must
have a degree of ingress protection IP≥6x (EN 60529).

• Use the electrical connection procedure in the Handbook.
• If possible, use galvanically-isolated equipment.
• Supply the Ex i equipment connected to the device. Use only certified intrinsically-safe

equipment.

• Connect only to separate certified, intrinsically-safe circuits. Make sure that the electrical

circuit characteristics are not more than the values that follow.

• Do not remove more than 6 mm / 0.2¨ of insulation from the wire.

3.5.2 Maximum intrinsically-safe values for the electrical circuit

3.5.3 Supply voltage

Level transmitter with the 4...20 mA output option

Level transmitter with the PROFIBUS PA or FOUNDATION fieldbus output options

Output option

Intrinsically-safe values for the electrical circuit

U

i

I

i

P

i

C

i

L

i

[V]

[mA]

[W]

[nF]

[µH]

4...20 mA passive - HART

≤30

≤300

≤1

=30

=30

PROFIBUS PA

FOUNDATION™ fieldbus

Entity

≤24

≤300

≤1.2

=1

=0

FISCO

≤17.5

≤380

≤5.32

=1

=0

Minimum voltage at

output terminal [VDC]

Maximum voltage at

output terminal [VDC]

Current output terminal

12

1

30

1

1 For a current output of 22 mA

Minimum voltage at

output terminal [VDC]

Maximum voltage at

output terminal [VDC]

Output terminal

Entity

9

24

FISCO

9

17.5