INSTALLATION

12

OPTIWAVE 5200 C/F

www.krohne.com

04/2013 - 4001905802 - AD ATEX OPTIWAVE 5200 R02 en

2.2 Operating conditions

The allowable ambient temperature and corresponding flange temperature range for the device
depends on the ATEX equipment category, IEC equipment protection level (EPL) and
temperature classes marked on the nameplate.

2.2.1 Ambient and flange temperature

The ATEX equipment category, IEC equipment protection level and temperature class give the
ambient temperature and related flange temperature ranges for the device.

For more data, refer to "Pressure and temperature ranges" in the Installation chapter of the
handbook.

WARNING!
The gasket temperature must be in the approved limits. The minimum gasket temperature is:

The gasket temperature must be in the approved limits. The minimum gasket temperature is:

The gasket temperature must be in the approved limits. The minimum gasket temperature is:

The gasket temperature must be in the approved limits. The minimum gasket temperature is:

Gasket material

Antenna type

Minimum process connection temperature

[°C]

[°F]

PFA

Metallic Horn

Wave-Guide

-60

-76

EPDM

-50

-58

FKM/FPM

-40

-40

Kalrez

®

6375

-20

-4

-

PTFE Wave Horn

-50

-58

-

PP Wave Horn

Wave-Stick

-20

-4

Definitions

Figure 2-2: Definitions

1 Compact version: Signal converter, process connection and antenna
2 Remote (Field) version: remote converter
3 Remote (Field) version: antenna housing, process connection and antenna