Modbus protocol – KROHNE IFC 100 Converter Modbus EN User Manual
Page 15
MODBUS PROTOCOL
6
15
IFC 100
www.krohne.com
08/2014 - 4001410101 - AD Modbus IFC 100 R01 en
43002
3002
limitation high
limitation high
limitation high
limitation high [m/s]
C1.2.1
float
2
43004
3004
time constant
time constant
time constant
time constant [s]
C1.2.3
float
2
43006
3006
pulse width
pulse width
pulse width
pulse width [s]
only if pulse filter is set to 1: on
C1.2.5
float
2
43008
3008
pulse limitation
pulse limitation
pulse limitation
pulse limitation [m/s]
C1.2.6
float
2
43010
3010
noise level
noise level
noise level
noise level [m/s]
C1.2.8
float
2
43012
3012
noise suppression
noise suppression
noise suppression
noise suppression
C1.2.9
float
2
43014
3014
low flow cutoff value
low flow cutoff value
low flow cutoff value
low flow cutoff value [m/s]
C1.2.10
float
2
43016
3016
limit empty pipe
limit empty pipe
limit empty pipe
limit empty pipe [S/m]
C1.3.3
float
2
43018
3018
no function
float
2
43020
3020
no function
float
2
43022
3022
limit electrode noise
limit electrode noise
limit electrode noise
limit electrode noise [m/s]
C1.3.14
float
2
43024
3024
Zero point
Zero point
Zero point
Zero point [m/s]
C1.1.1
float
2
43026
3026
Coil Resistance Rsp, 20
Coil Resistance Rsp, 20
Coil Resistance Rsp, 20
Coil Resistance Rsp, 20 [Ω]
C1.1.7
float
2
43028
3028
Coil Temperature Calpoint
Coil Temperature Calpoint
Coil Temperature Calpoint
Coil Temperature Calpoint [K]
C1.1.8
float
2
43030
3030
Coil Resistance Calpoint
Coil Resistance Calpoint
Coil Resistance Calpoint
Coil Resistance Calpoint [Ω]
C1.1.8
float
2
43032
3032
Electrode Factor EF
Electrode Factor EF
Electrode Factor EF
Electrode Factor EF [m]
C1.1.11
float
2
43034
3034
Conductivity Calpoint
Conductivity Calpoint
Conductivity Calpoint
Conductivity Calpoint [S/m]
C1.1.11
float
2
43036
3036
Conductivity Calpoint
Conductivity Calpoint
Conductivity Calpoint
Conductivity Calpoint [S/m]
C1.1.11
float
2
43038
3038
pulse width
pulse width
pulse width
pulse width [s]
only if pulse filter is set to 2: automatic
C1.2.5
float
2
Modbus protocol
address
Description and settings
Converter Fct.
No.
Type
Number of
registers
1st
2nd
.book Page 15 Monday, July 28, 2014 11:32 AM