6
MODBUS PROTOCOL
12
IFC 100
www.krohne.com
08/2014 - 4001410101 - AD Modbus IFC 100 R01 en
6.7 Input registers
All input registers in the Modbus protocol address range from 30000 to 38998 are mapped into
the range 0 to 8998. All input registers in the Modbus protocol address range from 20000 to
20998 are mapped into the range 9000 to 9998. This is done to give systems with restriction on
the address range access to the device.
Measurement and status values are read only and can be accessed as Modbus "Input Registers".
Cyclic GDC objects are mapped to Modbus Registers.
Function code is 04 (0x04).
Input register 30018 is not used up to now. This is included to fill the gap between the float and
double float values and allows to read the full range of registers.
Modbus protocol
address
Description and settings
Type
Number of registers
1st
2nd
30000
0
flow speed
flow speed
flow speed
flow speed [m/s]
float
2
30002
2
volume flow
volume flow
volume flow
volume flow [m
3
/s]
float
2
30004
4
mass flow
mass flow
mass flow
mass flow [kg/s]
float
2
30006
6
coil temperature
coil temperature
coil temperature
coil temperature [K]
float
2
30008
8
conductivity
conductivity
conductivity
conductivity [S/m]
This value may not be measured.
Depending on register (4)2003.
0 = off (not measured)
1 = conductivity [S/m]
2 = cond. + empty pipe (S) [S/m]
3 = cond. + empty pipe (F) [S/m]
4 = cond. + empty pipe (I) [S/m]
float
2
30010
10
diagnosis value
diagnosis value
diagnosis value
diagnosis value
This value may not be measured.
Depending on register (4)2011.
25 = off (not measured)
31 = electrode noise [m/s]
8 = terminal 2 DC [Volt]
9 = terminal 3 DC [Volt]
float
2
30012
12
Display Channel 1
Display Channel 1
Display Channel 1
Display Channel 1
Represents the value on the first line of
the first measurement screen in SI units
float
2
30014
14
Display Channel 2
Display Channel 2
Display Channel 2
Display Channel 2
Represents the value on the first line of
the second measurement screen in SI
units
float
2
30016
16
Operating time
Operating time
Operating time
Operating time [s]
float
2
30018
18
Not used, returns zero
float
2
30020
20
Counter 1
Counter 1
Counter 1
Counter 1 [m
3
] or [kg]
double float
4
30024
24
Counter 2
Counter 2
Counter 2
Counter 2 [m
3
] or [kg]
double float
4
30028
28
Not used, returns zero
double float
4
30032
32
long status sensor
long status sensor
long status sensor
long status sensor
byte [4]
2
30034
34
long status device
long status device
long status device
long status device
byte [4]
2
.book Page 12 Monday, July 28, 2014 11:32 AM