MODBUS PROTOCOL

6

13

IFC 100

www.krohne.com

08/2014 - 4001410101 - AD Modbus IFC 100 R01 en

Also the result of a calibration procedure is accessed by an input register at Modbus Protocol
Address 20000 or 9000. The type are one or more float values. This is depending on the used
function (refer to "Calibration procedures").

6.8 Holding registers

All holding registers in the Modbus protocol address range from 40000 to 49998 are mapped into
the range 0 to 9998. This is done to give systems with restriction on the address range access to
the device.

Some parameters of the device can be accessed as Modbus "holding registers".

Function code 03 (0x03) for "Read" operations and function code 16 (0x10) for "Write" operations.

The holding registers are grouped into the following different sections.

6.8.1 Counter parameters

Modbus protocol
address

Description and settings

Type

Number of registers

1st

2nd

20000

9000

Result of a calibration function

one or more float

values

2 times number of

values

Modbus protocol
address

Description and settings

Converter Fct.
No.

Type

Number of
registers

1st

2nd

40000

0

counter 1 function

counter 1 function

counter 1 function

counter 1 function

1 = sum counter

2 = + counter

3 = - counter

0 = off

C3.1.1

byte

1

40001

1

measurement Cnt1

measurement Cnt1

measurement Cnt1

measurement Cnt1

21 = volume flow

22 = mass flow

C3.1.2

word

1

40002

2

counter 2 function

counter 2 function

counter 2 function

counter 2 function

1 = sum counter

2 = + counter

3 = - counter

0 = off

C3.2.1

byte

1

40003

3

measurement Cnt2

measurement Cnt2

measurement Cnt2

measurement Cnt2

21 = volume flow

22 = mass flow

C3.2.2

word

1

40004

4

no function

byte

1

40005

5

no function

word

1

41000

1000

low flow cutoff value Cnt1

low flow cutoff value Cnt1

low flow cutoff value Cnt1

low flow cutoff value Cnt1 [m

3

/s] or [kg/s]

C3.1.3

float

2

41002

1002

time constant Cnt1

time constant Cnt1

time constant Cnt1

time constant Cnt1 [s]

C3.1.4

float

2

41004

1004

set counter Cnt1 or read Cnt1

set counter Cnt1 or read Cnt1

set counter Cnt1 or read Cnt1

set counter Cnt1 or read Cnt1 [m

3

] or [kg]

C3.1.7

float

2

41006

1006

low flow cutoff value Cnt2

low flow cutoff value Cnt2

low flow cutoff value Cnt2

low flow cutoff value Cnt2 [m

3

/s] or [kg/s]

C3.2.3

float

2

41008

1008

time constant Cnt2

time constant Cnt2

time constant Cnt2

time constant Cnt2 [s]

C3.2.4

float

2