Modbus protocol, 8 holding registers – KROHNE IFC 100 Converter Modbus EN User Manual
Page 13
MODBUS PROTOCOL
6
13
IFC 100
www.krohne.com
08/2014 - 4001410101 - AD Modbus IFC 100 R01 en
Also the result of a calibration procedure is accessed by an input register at Modbus Protocol
Address 20000 or 9000. The type are one or more float values. This is depending on the used
function (refer to "Calibration procedures").
6.8 Holding registers
All holding registers in the Modbus protocol address range from 40000 to 49998 are mapped into
the range 0 to 9998. This is done to give systems with restriction on the address range access to
the device.
Some parameters of the device can be accessed as Modbus "holding registers".
Function code 03 (0x03) for "Read" operations and function code 16 (0x10) for "Write" operations.
The holding registers are grouped into the following different sections.
6.8.1 Counter parameters
Modbus protocol
address
Description and settings
Type
Number of registers
1st
2nd
20000
9000
Result of a calibration function
one or more float
values
2 times number of
values
Modbus protocol
address
Description and settings
Converter Fct.
No.
Type
Number of
registers
1st
2nd
40000
0
counter 1 function
counter 1 function
counter 1 function
counter 1 function
1 = sum counter
2 = + counter
3 = - counter
0 = off
C3.1.1
byte
1
40001
1
measurement Cnt1
measurement Cnt1
measurement Cnt1
measurement Cnt1
21 = volume flow
22 = mass flow
C3.1.2
word
1
40002
2
counter 2 function
counter 2 function
counter 2 function
counter 2 function
1 = sum counter
2 = + counter
3 = - counter
0 = off
C3.2.1
byte
1
40003
3
measurement Cnt2
measurement Cnt2
measurement Cnt2
measurement Cnt2
21 = volume flow
22 = mass flow
C3.2.2
word
1
40004
4
no function
byte
1
40005
5
no function
word
1
41000
1000
low flow cutoff value Cnt1
low flow cutoff value Cnt1
low flow cutoff value Cnt1
low flow cutoff value Cnt1 [m
3
/s] or [kg/s]
C3.1.3
float
2
41002
1002
time constant Cnt1
time constant Cnt1
time constant Cnt1
time constant Cnt1 [s]
C3.1.4
float
2
41004
1004
set counter Cnt1 or read Cnt1
set counter Cnt1 or read Cnt1
set counter Cnt1 or read Cnt1
set counter Cnt1 or read Cnt1 [m
3
] or [kg]
C3.1.7
float
2
41006
1006
low flow cutoff value Cnt2
low flow cutoff value Cnt2
low flow cutoff value Cnt2
low flow cutoff value Cnt2 [m
3
/s] or [kg/s]
C3.2.3
float
2
41008
1008
time constant Cnt2
time constant Cnt2
time constant Cnt2
time constant Cnt2 [s]
C3.2.4
float
2
.book Page 13 Monday, July 28, 2014 11:32 AM