beautypg.com

KEPCO RA 19-8B Quick Start Guide User Manual

Page 4

background image

4

228-1681

080309

KEPCO, INC. 131-38 SANFORD AVENUE FLUSHING, NY. 11355 U.S.A. TEL (718) 461-7000 FAX (718) 767-1102

http://www.kepcopower.com email: [email protected]

FIGURE 3. BACKPLATE, INTERIOR VIEW, DIP SWITCHES AND KEYING

PARALLEL OPERATION. The most common use for

the RA 19-(X)B rack adapter is with two or more HSF’s
connected in parallel to a single load with forced current
sharing to increase current output, increase reliability and/
or provide redundancy. Only adjacent slots can be con-
nected in parallel using DIP switches.

Figure 4 shows HSF’s in slots 2 and 3 connected in paral-
lel (master/slave, master established automatically by
voltage) with forced current sharing and a close-on-fail
alarm circuit. Both HSF modules are configured for output
voltage to be adjusted from the front panel trimpot (factory
default setting). See HSF operator manual for other output
voltage adjustment options.

Configure DIP 4:

1. Set positions 1 and 2, to ON. This connects +S to +V

and –S to –V for slot 4, establishing local sensing for
slot 4 if slot 4 is to be used.

2. Set positions 3 and 4, to OFF. This isolates sense lines

(±S) between slots 4 and 3.

3. Set position 5 to OFF. This isolates the current share

bus (CB) between slots 4 and 3.

4. Set position 6 and 7, to OFF. This isolates the ALARM

(N.O.) and ALARM (COM) lines between slots 4 and 3.

5. Set position 8 to OFF. This position is only set to ON for

open-on-fail alarm circuits.

Configure DIP 3:

6. Set positions 1 and 2, to ON. This connects +S to +V

and –S to –V for slot 3, establishing local sensing for
slot 3.

7. Set positions 3 and 4, to ON. This connects sense lines

(+S to +S and –S to –S) for slots 3 and 2.

8. Set position 5, to ON. This connects the current share

bus (CB) for slots 3 and 2.

9. Set positions 6 and 7 to ON. Position 6 connects the

normally open ALARM (N.O.) lines and position 7 con-
nects the ALARM (COM) (common) for slots 3 and 2,
implementing a close-on-fail alarm circuit (see equiva-
lent schematic shown in Figure 4. If either PS2 or PS3
fails, a contact closure provides continuity across pins 7
and 14 of both I/O 4 and I/O 3.

10.Set position 8 to OFF. This position is only set to ON

for open-on-fail alarm circuits.

This manual is related to the following products: