Supplement to the MS-9600(UD)LS(C/E) Manual Revision B P/N 53587:A 03/20/09

3

This Supplement provides updates to the MS-9600(UD)LS(C/E) FACP manual Revision B as indicated below:

1 Table 5.3: System Current Draw Calculations on page 177

The following table provides updated current draw values. The current draws that have changed are indicated by bold
text.

Device Type

Calculation Column 1
Primary, Non-Fire Alarm Current
(amps)

Calculation Column 2
Primary, Fire Alarm Current
(amps)

Calculation Column 3
Secondary, Non-Fire Alarm Current
(amps)

Qty

X[current draw]=

Total

Qty

X [current draw] =

Total

Qty

X[current draw]=

Total

Main Circuit Board

1

X[0.160]=

0.160

1

X[0.253]=

0.253

1

X[0.103]=

0.103

ANN-80

[ ]

X[0.037]=

[ ]

X[0.040]=

[ ]

X[0.015]=

ANN-(R)LED

[ ]

X[0.028]=

[ ]

X[0.068]=

[ ]

X[0.028]=

ANN-RLY

[ ]

X[0.015]=

[ ]

X[0.075]=

[ ]

X[0.015]=

ANN-I/O

[ ]

X[0.035]=

[ ]

X[0.200]=

[ ]

X[0.035]=

ANN-S/PG

[ ]

X[0.045]=

[ ]

X[0.045]=

[ ]

X[0.045]=

ACM-8RF

[ ]

X[0.030]=

[ ]

X[0.158]

*

=

* All eight ACM-8RF relays activated on a single module.

[ ]

X[0.030]=

ACM-16ATF

ACM-32AF

[ ]

X[0.040]

[ ]

X[0.056]

=

† All annunciator LEDs on

[ ]

X[0.040]=

AEM-16ATF

AEM-32AF

[ ]

X[0.002]

[ ]

X[0.018]

2

=

[ ]

X[0.002]=

AFM-16ATF

AFM-32AF

[ ]

X[0.040]

[ ]

X[0.056]

2

=

[ ]

X[0.040]=

AFM-16AF

[ ]

X[0.025]

[ ]

X[0.065]

2

=

[ ]

X[0.025]=

DACT-UD2

[ ]

X[0.020]

[ ]

X[0.029]=

[ ]

X[0.017]=

LDM-32F

[ ]

X[0.040]

[ ]

X[0.056]

=

‡ LDM-32F with LEDs on

[ ]

X[0.040]=

LDM-E32F

[ ]

X[0.002]

[ ]

X[0.018]=

[ ]

X[0.002]=

LCD-80F & LCD-80FC

[ ]

X[0.064]

[ ]

X[0.064]=

[ ]

X[0.025]=

4XTMF

[ ]

X[0.005]=

[ ]

X[0.011]

**

=

** If using the Reverse Polarity Alarm output, add 0.005 amps; if using the Reverse Polarity Trouble output, add

another 0.005 amps.

[ ]

X[0.005]=

4-wire Detector Heads

[ ]

X[ ]

††

=

†† Refer to the Device Compatibility Document for standby current.

[ ]

X[ ]=

[ ]

X[ ]=

Power Supervision

Relays

‡‡

‡‡ Must use compatible listed Power Supervision Relay.

[ ]

X[0.025]=

[ ]

X[0.025]=

[ ]

X[0.025]=

SLC-2LS Expander

[ ]

X[0.02500]=

X[0.02600]=

[ ]

X[0.01900]=

CP350 & CP355

[ ]

X[0.00030]=

maximum alarm draw

for all devices:

with one (1) SLC Loop

with two (2) SLC Loops

0.400

0.800

[ ]

X[0.00030]=

SD350 & SD355

[ ]

X[0.00030]=

[ ]

X[0.00030]=

SD350T & SD355T

[ ]

X[0.00030]=

[ ]

X[0.00030]=

AD350 & AD355

[ ]

X[0.00030]=

[ ]

X[0.00030]=

H350 & H355

[ ]

X[0.00030]=

[ ]

X[0.00030]=

H350R & H355R

[ ]

X[0.00030]=

[ ]

X[0.00030]=

H355HT

[ ]

X[0.00030]=

[ ]

X[0.00030]=

D350P & D350PL

[ ]

X[0.00030]=

[ ]

X[0.00030]=

D350RP & D350RPL

[ ]

X[0.00030]=

[ ]

X[0.00030]=

B501BH &

B501BHT

***

***Maximum alarm current for each sounder base is 0.015 amps which must be supplied by aux. 24VDC source.

[ ]

X[0.001]=

[ ]

X[0.001]=

B224RB Relay Base

[ ]

X[0.00050]=

[ ]

X[0.00050]=

B224BI Isolator Base

[ ]

X[0.00045]=

[ ]

X[0.00045]=

MMF-300

[ ]

X[0.00040]=

[ ]

X[0.00040]=

MMF-300-10

[ ]

X[0.00350]=

[ ]

X[0.00350]=

MDF-300

[ ]

X[0.00075]=

[ ]

X[0.00075]=

MMF-301

[ ]

X[0.000375]=

[ ]

X[0.000375]=

MMF-302

[ ]

X[0.00027]=

[ ]

X[0.00027]=

MMF-302-6

[ ]

X[0.00200]=

[ ]

X[0.00200]=

BG-12LX

[ ]

X[0.00030]=

[ ]

X[0.00030]=

CMF-300

[ ]

X[0.00039]=

[ ]

X[0.00039]=

CMF-300-6

[ ]

X[0.00225]=

[ ]

X[0.00225]=

CRF-300

[ ]

X[0.00027]=

[ ]

X[0.00027]=

CRF-300-6

[ ]

X[0.00145]=

[ ]

X[0.00145]=

I300

[ ]

X[0.00040]=

[ ]

X[0.00040]=

NAC #1

†††

†††Current limitation of Terminal TB4 circuits is 3.00 amps per NAC.

[ ]

X[ ]=

NAC #2

[ ]

X[ ]=

NAC #3

[ ]

X[ ]=

NAC #4

[ ]

X[ ]=

Current Draw from TB3

(nonalarm

‡‡‡

)

‡‡‡The total standby current must include both the resettable (TB3 Terminals 1 & 2) and nonresettable (TB3

Terminals 3 & 4, 5 & 6) power. Caution must be taken to ensure that current drawn from these outputs during
alarm does not exceed maximum ratings specified. Current limitations of TB3 circuits is 3.0 amps per output

[ ]=

[ ]

[ ]=

[ ]

[ ]=

Sum each column

****

for totals

****Total current draw listed above cannot exceed 7.0 amps in alarm.

Primary Non-Alarm =

Primary Alarm =

Secondary Non-Alarm =