Product Installation Drawing
Document Number 15275 Rev B
ECN: 97-192 Print Date: 7/7/97
RZA-4XF Remote Ann
RZA-4XF Remote Ann
RZA-4XF Remote Ann
RZA-4XF Remote Ann
RZA-4XF Remote Annunciator
unciator
unciator
unciator
unciator
The RZA-4XF Remote Annunciator mounts on a standard single-gang
box, and provides LED indication of the same functions as the 4XZMF
Zone Relay Module. For example, with DIP 1=ON and DIP 2=OFF:
• One Zone in Alarm (red)
• Two Zones in Alarm (red)
• Releasing Circuit 1 (red)
• Releasing Circuit 2 (red)
•
•
•
•
• System Trouble (yellow)
A Local Trouble Sounder and Silence Switch are also provided. All LED
wiring is supervised for open conditions. Any open condition will cause
the System Trouble LED to illuminate.
✍
Note:
Note:
Note:
Note:
Note: The RZA-4XF Remote Annunciator requires the use of an
LED Interface Module (see Figure 1, reverse side).