beautypg.com

Fire-Lite MS-9200UDLS Keltron RCVR/XMTR Wiring Diagram User Manual

Wiring diagram

background image

Document 52776 Rev A November 04, 2005

FACP

with Keltron RCVR/XMTR

Wiring Diagram

52776 Revision A

November 04, 2005

Keltron 95M3158 TTM-RPS

1. Terminals 7 and 8: Remote station alarm/trouble inputs.
2. Terminals 9 and 10: Sprinkler supervisory input.

Sprinkler Supervisory Signal

Alarm/Trouble Signal

* Note: For more information,
refer to Keltron manual.

ECN 05-680

4XTMF

Note: Cut TBL jumper on 4XTMF/4XTM
module to send alarm/trouble signal from
the same pair of terminals.

CAUTION!

For reasons of wiring diagram clarity, terminal designa-
tions of Keltron modules are not shown in actual order.
Follow Keltron manual and module markings for exact ter-
minal locations to prevent severe module damage!

Fire Alarm Control Panel

(terminal blocks not shown in actual
positions)

(24 VDC,
Non-Resettable)

4XTMF Module