beautypg.com

Fire-Lite MS-9200(C)/E Field Software Change Procedure (and programming existing MS-9200 Systems for use with the LCD-40) User Manual

Page 3

background image

Document 50053 Rev M 1/10/08 P/N 50053:M

3 of 5

LCD-40 installation in an existing MS-9200(C)/E

In an existing MS-9200(C)/E installation, the following procedure must be followed to program the MS-9200(C)/E for
use with the LCD-40 Series Annunciator:

1. Connect the LCD-40 to the MS-9200(C)/E Control Panel (refer to the appropriate MS-9200(C)/E Technical

Manual and Product Installation Drawings).

2. Software Versions:

(1) If software with either the Part Number 73750 or 73829 is installed in the MS-9200(C), the LCD-40

Series Annunciator must have software with a Part Number of 73779 or 73879 to operate with the
FACP (Fire Alarm Control Panel). If software with a Part Number of #M9200V20 or higher is installed
in the MS-9200(C), the LCD-40 Series Annunciator must have software with a Part Number of
#LCD40V20 or higher to operate with the FACP.

(2) If software with Part Number 73846 is installed in the MS-9200E, the LCD-40 Series Annunciator

must have software with Part Number 73779 or 73879 to operate with the FACP. If software with
Part Number #M9200EV20 or higher is installed in the MS-9200E, the LCD-40 Series Annunciator
must have software with a Part Number of #LCD40V20 or higher to operate with the FACP.

3. Upon initial power-up of the MS-9200(C)/E with the new software installed, the following message may

appear on the MS-9200(C)/E LCD display:

"TROUBLE IN SYSTEM
PROGRAM CORRUPTED"

Whether the above message appears or not, the following steps must be followed to program the
MS-9200 for use with the LCD-40.

4. Press the ENTER key.
5. Press the 1 key to select Programming.
6. Enter your LEVEL 1 password.
7. Press the ENTER key.
8. Press the 1 key to select Autoprogram.
9. Upon successful completion of the Autoprogram function, press the LEFT ARROW key.
10. Press the 3 key to select System Edit.
11. At this point, use the RIGHT ARROW key to select TRM = N (or L/P = N as shown in the manual).
12. Press the UP ARROW key to change 'N' to 'L' in order to program the system for LCD-40 use.
13. Be sure to press the ENTER key to store the programming change in memory.
14. Press the LEFT ARROW key several times to get back to the SYSTEMS ALL NORMAL display.
15. At this point, the MS-9200(C)/E should be successfully programmed for use with the LCD-40. To ensure

that all programming changes have been accepted, depress the RESET key. The system should return
to the SYSTEMS ALL NORMAL display, after a successful software check.