Fire-Lite LCD-80F Remote LCD Annunciator User Manual
Page 17

Operation
Switch Functions
17
Document 51338 Rev. B 08/24/05 P/N 51338:B
When more than one event exists, the first press of the Acknowledge 
switch silences system piezo sounders. The second press of the 
switch stops the scrolling and holds the event on the display for one 
minute. Subsequent pressing of the switch 'steps' through each 
active event.
2.2.3 Silence
When the Silence switch is pressed and released, the LCD-80F sends 
an alarm silence command to the control panel. The Silence switch 
performs the same functions as the Acknowledge switch. In 
addition, if an alarm exists, it turns off all silenceable NACs and 
causes the FACP Alarm Silenced LED to turn on while the LCD-80F 
will display a 'silenced' message. It also sends an 'Alarm Silenced' 
message to the printer and the history file within the FACP. A 
subsequent new alarm will resound the appropriate NACs (Notifica-
tion Appliance Circuits) and local sounders.
2.2.4 Drill: Hold 2 Sec.
When the Drill switch is pressed and held for at least two seconds 
(time required to prevent accidental activations), the LCD-80F will 
transmit a drill command to the control panel. This command causes 
the FACP to turn on all NAC outputs and all silenceable circuits (all 
control modules/NACs that are programmed silenceable). In the 
event that the system was previously silenced, the drill command 
will also turn off the Alarm Silenced LED. The 'Manual Evacuate' 
message is shown on the LCD-80F display. The same message is 
sent to the FACP display, printer and history files. The Silence 
switch operates on silenceable NAC outputs only.
2.2.5 Reset
When the System Reset switch is pressed and released, the LCD-80F 
sends a Reset command to the control panel. This will turn off all 
control modules and Notification Appliance Circuits, temporarily 
turns off resettable power to 4-wire detectors, causes a 'System All 
Normal' message to be displayed on the LCD-80F and sends a 
'System Reset' message to the FACP display, printer and FACP 
history files. It also turns on all system LEDs, piezo sounders and 
LCD display segments as long as the Reset switch is held (lamp 
test). Any alarm or trouble that exists after a Reset will resound the 
system.