Iii - 3.1.3 – Fire-Lite IPDACT-2 User Manual
Page 35

IPDACT-2(UD) - Configuration
III-32
Doc.DM385-I
Rev. 4.0
The register is made up of four fields corresponding to the 4 numbers of the IP 
address; this admits values between 0 and 255. Each number has a 
verification digit. The default value is: 
000
000
000
000
Alarm encryption key for the IPDACT-2(UD) to the maintenance receiver
This is the key used by the IPDACT-2(UD) to send alarms to the Teldat 
maintenance VisorALARM. So the configuration is valid, this must be 
repeated twice. 
The registrar consists of one field with up to 16 DTMF digits. By default, no 
value is configured. 
Autoregister password
This is a password for the IPDACT-2(UD) to perform a delayed registration in 
the configured VisorALARM receiver and consequently get the full 
configuration parameters needed for operating purposes. 
It must match the Installation Password defined in the Configuration Patterns 
in the VisorALARM receiver that corresponds to the parameter set that must 
be downloaded in the IPDACT-2(UD). 
From this moment the IPDACT starts trying to connect the VisorALARM to 
complete registration and start operating. 
While the IPDACT is in the auto-registering process, LED A flashes green. 
When the registration has completed, LED A stops flashing and LED E lights 
up in green. 
Using the testing digits
In order to increase the reliability of the telephonic console, some registers 
require an additional testing digit in each of their fields so that if the control 
digit does not adjust to the introduced value, the data is considered invalid 
and an error tone is emitted. This facility can be enabled or disabled through 
this register. 
The register is made up of a single digit field which admits a value of 1 to 
activate the use of the testing digits and value 0 to deactivate. The fields 
contain a verification digit for the number. Default value is 0. 
III - 3.1.3.
Minimum configuration for the installer
By using the configuration patterns in the Teldat VisorALARM, you can 
simplify the IPDACT-2(UD) installation process. So that the whole of the 
process is possible, it is essential that there is a configuration pattern 
configured in the VisorALARM. In the pattern, an installer password is 
associated to a given IPDACT-2(UD) configuration. This configuration 