Fire-Lite IPDACT-2 User Manual

Ipdact-2/ipdact-2ud, Ip communicator

background image

IPDACT-2/IPDACT-2UD

IP Communicator

IPDACT-2(UD) Dm 387-Iv3

Quick Start Programming Guide using a PC Serial Port

Model TS563/2

1

. Requirements

Alarm Panel

• “Contact Id” compatible panel with tone dialing.
• Existing PSTN Service (for backup communication lines).
• PC with RS-232 serial port.

Console cable for the IPDACT-2(UD).

Power

Voltage Range

10-28 VDC

Current (Maximum) 12VDC

IPDACT-2: 180 mA (NSC), 230 mA (Alarm)

IPDACT-2UD: 185 mA (NSC), 230 mA (Alarm)

Current (Maximum) 24VDC

IPDACT-2: 93 mA (NSC), 136 mA (Alarm)

IPDACT-2UD: 98 mA (NSC), 155 mA (Alarm)

Internet Access

Either a static IP address (always the same) or a dynamic IP address (could be different every time
a connection is made) are possible.

2. Checklist¹

a.

IPDACT-2(UD) console access password (default is 24680).

b.

Installer password, required to execute the register command.

c.

IP address, subnet mask and gateway for IPDACT-2(UD)

2

d.

IPDACT-2(UD) account number or client number.

e.

IP address, and UDP Port number of the VisorALARM central station.

1

Please obtain the following information from your central monitoring station.

2

If you have a DHCP server in the network to which the IPDACT-2(UD) connects, these parameters can be obtained automatically.