Resetting the Pull Station

1. Insert the key into the lock and rotate 1/4 turn coun-

terclockwise.

2. Open the door until the handle returns to normal.

3. Close and lock the door.

Note: Closing the door automatically resets the switch to the
‘Normal’ position. Opening the door will not activate or deactivate
the alarm switch.

Wiring and Assembly Instructions

1. Surface mount the Outdoor Backbox (WBB) using

the incorporated flanges.

2. Pull all necessary wiring through the mounted back-

box.

3. Using the built-in strip gauge, on the back of the pull

station, remove the correct amount of wire insulation.

4. Connect the wiring from the FACPs Initiating Device

Circuit (IDC), or any previous device on the IDC, to
terminals 1 and 2 on the pull stations terminal strip.

5. Connect the next device on the IDC, or an End-or-

Line Resistor (ELR), to terminals 1 and 2.

6. Connect the wiring from the auxillary circuit to termi-

nals 3 & 4.

Note: Maintain consistent polarity with all connections throughout
the IDC.

Note: Do not loop wiring under any terminals. Break wire run to
maintain IDC supervision.

7. Attach the pull station to the backbox using the (4)

8-32 x .375” screws provided.

Caution

Install the pull station in accordance with the supplied
instructions, applicable NFPA standards, national and
local Fire and Electrical codes and the requirements of the
Authority Having Jurisdiction (AHJ). Conduct regular
testing of the devices using appropriate NFPA standards.
Fire•Lite is not responsible for devices that have not been
properly installed, tested and maintained.

ADA Compliance

For ADA compliance, if the clear floor space only allows
forward approach to an object, the maximum forward
reach height allowed is 48-inches (121.92cm). If the clear
floor space allows parallel approach by a person in a
wheelchair, the maximum side reach allowed is 54-inches
(137.16cm).