beautypg.com

A.O. Smith BTH 120 - 250 User Manual

Page 14

background image

14

HEATER WIRING

IF ANY OF THE ORIGINAL WIRE AS SUPPLIED WITH THE APPLIANCE

MUST BE REPLACED, IT MUST BE REPLACED WITH 105°C WIRE OR ITS

EQUIVALENT, EXCEPT IN THE BURNER HOUSING. IN THIS CASE USE

200°C WIRE.

THE COMPUTER CONTROL REQUIRES A SOURCE OF STABLE CLEAN

ELECTRICITY FOR PROPER OPERATION. INSTALLING THE HEATER ON

A BRANCH CIRCUIT THAT HAS ELECTRONIC NOISE, IS SUBJECT TO

FLUCTUATIONS IN VOLTAGE LEVEL OR HAS AN APPLIANCE WHICH

GENERATES EMF OF RFI INTERFERENCE CAN CAUSE THE

CONTROLLER TO MALFUNCTION. A HIGH QUALITY POWER

CONDITIONER MUST BE INSTALLED IF THE ABOVE CONDITIONS EXIST.

MALFUNCTIONS CAUSED BY A POOR ELECTRICAL SUPPLY ARE NOT

COVERED UNDER YOUR WARRANTY.

The controller is wired to the heater as shown in figures 16 & 17. The

model and rating plate provides the electrical information needed to

size the complete heater branch supply.

All electrical work must be installed in accordance with the National

Electrical Code and local requirements.

When installed, the appliance must be electrically grounded in

accordance with local codes or, in the absence of local codes, with

the National Electrical Code, ANSI/NFPA 70.

DO NOT ENERGIZE THE BRANCH CIRCUIT BEFORE THE HEATER TANK

IS FILLED WITH WATER.

NOTE: This controller is Polarity Sensitive. If the Hot and Neutral Supply

Voltage is reversed, the controller will not sense flame. Verify polarity

before connecting the unit.

WATER LINE CONNECTIONS

This manual provides detailed installation diagrams (see back section of

this manual) for typical methods of application for the water heaters.

The water heater may be installed by itself, or with a separate storage

tank. When used with a separate storage tank, the circulation may be

either by gravity or by means of circulating pump. When a circulating pump

is used, it is important to note that the flow rate should be slow so that there

will be a minimum of turbulence inside the heater.

CLOSED SYSTEM

CAUTION

A closed system will exist if a check valve (without bypass), pressure

reducing valve (without bypass), or a water meter (without bypass) is

installed in the cold water line between the water heater and street main

(or well).

Excessive pressure may develop causing premature tank failure or

intermittent relief valve operation. This type of failure is not covered by the

limited warranty. An expansion tank or a similar device may be required in

the inlet supply line between the appliance and the meter or valve to

compensate for the thermal expansion of water under supply pressure.

If a water heater is installed in a closed water system, check local codes

or contact the water supplier or local plumbing inspector on how to control

this situation.

FIGURE 16

BSR BOARD (BTH - 250 ONLY)