8.4 Optional Type Z Enclosure Purge Assembly


Model X40 controllers are available with an optional, externally mounted, Model 1001A Z-Purge system.
This purge assembly achieves a Class 1, Division 2, Group CD area classification. The Type Z-Purge
assembly is installed on the X40 Controller at the Detcon factory.

The Z-Purge option is factory wired to automatically removed AC power from the controller if there is a
loss of pressure. The Z-Purge is not wired to removed DC Power or battery backup power from the unit. It
is the responsibility of the user to manually shut off all power sources if pressure is lost or the X40
Controller enclosure is opened.

The Type Z purge option includes a factory installed bypass switch that can be used to continue operation
of the Model X40 Controller even when the NEMA 4X enclosure is opened and the purge system pressure
is lost. The bypass switch can be toggled between Bypass and Normal, where in the Bypass mode the
purge protection and Class 1 Div 2 area classification is lost.

NOTE1: The Z-Purge option is factory wired to automatically removed AC power from the controller if
there is a loss of pressure. The Z-Purge is not wired to removed DC Power or battery backup power from
the unit. It is the responsibility of the user to manually shut off all power sources if pressure is lost or the
X40 Controller enclosure is opened.

NOTE2: Use of the purge bypass switch invalidates the Class 1 Div 2 area classification and should not be
done without proper authorization. When purge pressure is lost, Class 1 Div 2 area classification is lost
regardless.

The instruction manual for the Model 1001A Type Z purge system is supplied separately. Refer to this
manual for details on purge supply requirements.