beautypg.com

System features, 1 modbus communications, Modbus communications – Detcon 840 User Manual

Page 22

background image

840 Operators Manual

Model 840 Operator Manual

Rev. 1.9

Page 18 of 29

7.

System Features

7.1 Modbus Communications


The model 840 controllers feature a Modbus compatible communications protocol and are addressable by a
PLC, PC/HMI, DCS, or other Modbus RTU master-polling devices. Communication is accomplished by
two wire half duplex RS-485, 9600 baud, 8 data bits, 1 stop bit, no parity, through the controllers secondary
port. Wiring should be brought directly to J10 located on the motherboard.

A Modbus™ RTU master device up to 4000 feet away can theoretically poll up to 64 different controllers.
This number may not be realistic in harsh environments where noise and/or wiring conditions would make
it impractical to place so many devices on the same pair of wires. If a multi-point system is being utilized,
each controller must be set to a different device address.

Modbus™ Register Detail:
Code 03 - Read Holding Registers is the only code supported by the 840 controller.

Register #
40000

Channel 1 Reading

40001

Channel 2 Reading

40002

Channel 3 Reading

40003

Channel 4 Reading

40004

Channel 5 Reading

40005

Channel 6 Reading

40006

Channel 7 Reading

40007

Channel 8 Reading


40008 Fault Status Bits
High Byte
Bit 7

Not Used

Bit 6

Not Used

Bit 5

Not Used

Bit 4

Not Used

Bit 3

Not Used

Bit 2

Not Used

Bit 1

Not Used

Bit 0

Not Used

Low Byte
Bit 7

1 = Channel 8 Fault

0 = Channel 8 no Fault

Bit 6

1 = Channel 7 Fault

0 = Channel 7 no Fault

Bit 5

1 = Channel 6 Fault

0 = Channel 6 no Fault

Bit 4

1 = Channel 5 Fault

0 = Channel 5 no Fault

Bit 3

1 = Channel 4 Fault

0 = Channel 4 no Fault

Bit 2

1 = Channel 3 Fault

0 = Channel 3 no Fault

Bit 1

1 = Channel 2 Fault

0 = Channel 2 no Fault

Bit 0

1 = Channel 1 Fault

0 = Channel 1 no Fault

40009 Alarm 1 Status Bits
High Byte
Bit 7

Not Used

Bit 6

Not Used

Bit 5

Not Used