beautypg.com

Fig. #4, Typical sensor – Detcon 110A-FB User Manual

Page 7

background image

03. If applicable, connect the 24 VDC standby battery to the lugless terminal strip (labeled VDC IN) on the

controller motherboard (see figure #4). The DC current load is a maximum 1 amp.

Caution: Observe correct polarity when terminating all input/output field wiring. Failure to do so may
result in circuit damage on power up.

04. If applicable, connect a normally open momentary remote mounted switch to the lugless terminal strip

(labeled RESET) located on the controller motherboard (see figure #4).

05. Refer to installation and wiring detail of remote mount sensor assemblies as detailed in section 3.0.

Terminate field wiring from sensors to Model 110A-FB lugless terminal strips located on the controller
motherboard (see figure #4).

Note: Based on the application and use of relay contact outputs, complete all wiring terminations prior to
application of power. Shut-in controls may be omitted until system test is complete.

1.13 S

TART-UP

Upon completion of all field wiring, turn the unit on via the power switch located on the motherboard (see
figure #1). Note that the 110A-FB digital display illuminates. Varying readings may occur during sensor
warm-up. A 10 second alarm delay will occur on power up.

Detcon Model 110A-FB Gas Detection System PG.7

L1 L2

117

VAC IN

AUX 24
VDC IN

SENSOR

C

NC

NO

C

NC

NO

C

NC

NO

MA

FAULT

LOW

HIGH

4-20

madc
OUT

RESET

MA

24VDC

+

4-20MA

Typical Sensor

ALARM CONTACTS

Common, Normally Open

and Normally Closed

External Alarm Reset Switch
Normally Open Momentary

Fig. #4

Wiring Detail