beautypg.com

3 calibration, 4 maintenance, 5 warranty – Detcon Sensor Duct Mount Kit FP/TP/DM/IR Series User Manual

Page 7

background image

1.3 Calibration

CAUTION: In high velocity air ducts, air f low may need to be shut down before calibration takes place.

1 - Verify that there is no air f low through the duct.

2 - Remove the cal port plug.

3 - Apply the target gas to the cal port at a f low rate of 500 milliliter per minute for combustible (FP series)

and solid state H2S (TP series) sensors. Apply a f low rate of 1000 ml/m for toxic gas (DM series) sensors.

4 - Follow calibration instructions provided in the sensor instruction manual.

5 - Remove the target gas and apply a zero air standard for clearing.

6 - If necessary, repeat items 3-5 as indicated in the sensor instruction manual.

7 - Replace the cal port plug.

Calibration is complete.

1.4 Maintenance

To remove the sensor for replacement or maintenance, perform the following steps.

1 - Remove the two bolts that hold the sensor condulet to the duct mount plate.

2 - Pull the sensor out of the duct mount chamber and perform necessary maintenance.

3 - Reverse the procedure to replace the sensor. If necessary, lubricate the O’rings inside the duct mount

chamber so that the sensor rain shield will slide into the chamber easily.

1.5 Warranty

Detcon, Inc., as manufacturer, warrants each sensor duct mount kit for a period of one year under the condi-

tions described as follows: The warranty period begins on the date of shipment to the original purchaser and

ends one year thereafter. Should any part fail return the defective part to Detcon, Inc., for necessary repairs

or replacement.

Detcon Duct Mount Kit PG.7

Cal Port

Cal Gas Flow

Shipping Address: 3200 A-1 Research Forest Dr., The Woodlands, Texas 7381

Mailing Address: P.O. Box 8067, The Woodlands, Texas 77387-8067

phone 888-367-4286, 281-367-4100 • fax 281-292-2860 • www.detcon.com • [email protected]